User manual
49TPTQ-104C ♦ 48TQuantum Platform  Reference 
47TIEC 60870-5-104 Client 
  12TUser Manual 
  Local rack - The module must be placed in the same rack as processor 
  Compatible with all common Quantum programming packages, including 
Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), ProWORX 
(version 2.20 or later), and ModSoft 
  Quantum data types supported: 0x, 1x, 3x, 4x 
  High speed data transfer across backplane provides quick data update times 
9.1.4  Hardware Specifications 
Specification 
Value 
Backplane Current Load 
1100 mA maximum @ 5 Vdc ± 5% 
Operating Temperature 
0°C to 60°C (32°F to 140°F)  
Storage Temperature 
-40°C to 85°C (-40°F to 185°F)  
Relative Humidity 
5% to 95% (without condensation) 
Vibration 
Sine vibration 4-100 Hz in each of the 3 orthogonal 
axes 
Shock 
30G, 11 mSec. in each of the 3 orthogonal axes 
Dimensions (HxWxD), 
Approx. 
250 x 40.34 x 103.85 mm 
9.84 x 1.59 x 4.09 in 
LED Indicators 
Active Status 
Ethernet port Status 
Battery Status 
Debug/Config Port Activity  
Module Status 
Debug/Configuration Port (Debug) 
CFG Port (DEBUG) 
DB-9M PC Compatible 
RS-232 only 
No hardware handshaking 
Application Ports 
Application Ethernet port 
RJ45 Connector 
Link and Activity LED indicators 
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 
s, applied as specified in section 5.3.2 of IEC 60950: 
1991 
Ethernet Broadcast Storm Resiliency = less than or 
equal to 5000 [ARP] frames-per-second and less than 
or equal to 5 minutes duration 
9.1.5  Functional Specifications 
The PTQ-104C module sends data read/write commands to a server/slave on 
the network.  
The module has 4000 words of user defined internal register space that are 
accessible to the protocol driver and to the Quantum processor memory. Any of 
the supported database types can be individually located (within the total 
database size limit of 4000 words) and each database point is mapped within the 
module and can be assigned to one or more Groups. The supported IEC-870-5-
104 database point types are: 
Database Type 
Description 
Event Generation 
Point Size 
M_SP_NA 
Monitored single-point database 
State Change 
1 bit 
ProSoft Technology, Inc.  Page 107 of 136 
March 4, 2013 