49TPTQ-104C ♦ 48TQuantum Platform  Reference 
47TIEC 60870-5-104 Client 
  12TUser Manual 
9.2.3  Events 
The event pass-through functionality must be initially enabled by the user in PCB. 
The ‘Pass-Through Events’ parameter will need to be set to ‘Yes’ in the [Module] 
section. 
In order to improve communication efficiency, most applications will require the 
Client to periodically poll for data changes with a higher priority than polling for 
other monitored data. Every time a data point changes, the server can send this 
information as an event, typically with date and time information indicating when 
the change occurred. 
The following illustration shows the basic idea of the event pass-through 
functionality. When the module receives the event from the remote device, it will 
build block 9903, which will be copied to the processor at the configured memory 
address: 
The module supports a buffer queue of 99 events per data type. When the queue 
is full, the module will delete the oldest event in the queue, replacing it with the 
newest event received for that data type.  