12TUser Manual  47TIEC 60870-5-104 Client 
Sets the Block Number (9971=Write Module’s Time) and then increments the 
output sequence number (OutputControl[1]) by one. Once the module reads a 
new output sequence number from the processor it will process this request. So 
remember that the actual trigger is moving a new output block sequence number 
value to the module. Moving the block number (9970) is not the trigger to request 
this task from the module. MyTrigger is set to -1 as an indication that the logic is 
waiting for the response from the module. 
IF (MyTrigger=9971) THEN 
OutputControl1[1] :=MyTrigger; 
OutputControl1[2] :=SetTime.MyYear; 
OutputControl1[3] :=SetTime.MyMonth; 
OutputControl1[4] :=SetTime.MyDay; 
OutputControl1[5] :=SetTime.MyHour; 
OutputControl1[6] :=SetTime.MyMinute; 
OutputControl1[7] :=SetTime.MySecond; 
OutputControl1[8] :=SetTime.MyMillisecond; 
Temp:=WORD_TO_INT(OutputControl1[0]); 
Temp:=Temp+1; 
OutputControl1[0]:=INT_TO_WORD(Temp); 
END_IF; 
Once the request was processed the module will send the block response and 
increment the received output sequence number by 1. So the output sequence 
number is one less than the input sequence number the module has sent a new 
block. *). 
5.3.2  Read Status (Block 9250) 
This block is used to request status data from the module by the processor.  
Block Format from Processor (4x Register Data) sent to module 
Word Offset in Block 
Data Field(s) 
Description 
0 
Sequence 
Counter 
This field contains a new value each time the user 
wishes to request a new command block. 
1 
Block ID 
This field contains the block identification code of 9250 
for the block. 
2 to 63 
Spare 
Not used. 
Page 52 of 136  ProSoft Technology, Inc. 