User manual
49TPTQ-104C ♦ 48TQuantum Platform  Module Configuration 
47TIEC 60870-5-104 Client 
  12TUser Manual 
5.4.2  Time Zone 
-11 to 11 
This parameter specifies the time zone offset to be used from the UTC time 
zone. A value of zero uses UTC time. If the value entered is positive, the time 
zone is west of the UTC time zone (that is, Eastern Standard Time is 5). If the 
value entered is negative, the time zone is east of the UTC time zone (that is, 
Continental Europe is -1). 
5.4.3  Use Daylight Savings Time 
Yes or No 
This parameter specifies if daylight savings time will be used in the time 
computation. 
5.4.4  Database Register 
-1 or 0 to 3992 as an even value 
This parameter specifies if the NTP time computed by the driver is to be placed 
into the module’s database. If a value of -1 is specified, the time will not be 
placed into the database. If the value is between 0 and 3992, the time will be 
placed in the database. The first 4 bytes will represent the seconds since 
1/1/1970, and the second 4 bytes will represent the number of microseconds. An 
even value should be used for the register value in order for the data to be stored 
correctly. 
5.5  [IEC-104 Client Module] 
The [IEC-104 Client Module] section of PCB includes the general configuration of 
the 104C driver.  
ProSoft Technology, Inc.  Page 61 of 136 
March 4, 2013 