User manual
49TPTQ-104C ♦ 48TQuantum Platform  Module Configuration 
47TIEC 60870-5-104 Client 
  12TUser Manual 
5.6.1   [IEC-104 Client/Session x > IEC-104 Client x] section 
Item 
Range 
Description 
Server IP Address 
IP dotted 
notation 
IP address for the server to connect this client to 
with 0.0.0.0 used to disable the client. 
Sector Count 
1 or 2 
This parameter sets the number of sectors 
contained in this controlled device. The range of 
values is from 1 to 2. A sector section is required 
for each sector in a session to define its database 
and settings. 
T0 timeout 
1 to 30 
Number of seconds to wait for connection to be 
established with server in seconds (default=30) 
T1 timeout 
1 to 255 
Number of seconds until a timeout occurs to send 
or test APDU's (Application Protocol Data Units) 
(default = 15) 
T2 timeout 
1 to 255 
Number of seconds until timeout for non-data 
acknowledgement (t2 < t1) (default=10) 
T3 timeout 
1 to 300 
Timeout for test frame on idle state in seconds 
(default=20) 
k (maximum queue) 
1 to 12 
Maximum number of messages to hold in queue  
w (latest ack threshold) 
1 to 8 
Threshold value when to send ack. This 
parameter should be less than or equal to two-
thirds of k. 
Originator address for 
COT 
0 to 255 
Originator address in the COT (Cause of 
Transmission) to use in all messages from the 
client  
Response Timeout 
500 to 2^32-1 
This parameter sets the maximum number of 
milliseconds to wait for a confirmation from the 
controlled station to a request from this module to 
application level messages. 
ProSoft Technology, Inc.  Page 63 of 136 