User manual
49TPTQ-104C ♦ 48TQuantum Platform  Module Configuration 
47TIEC 60870-5-104 Client 
  12TUser Manual 
Item 
Range 
Description 
Enable Code 
Enable/Disable 
Disable = Disables command 
Enable = Enables command with Poll Interval in 
seconds 
Conditional = Executes command when point 
value in database changes 
Database Address 
This field specifies the location in the module's 
internal database to associate with the 
command. The Data Type (page 46) used in the 
command determines addressing of the index 
as follows: 
Data Type 
Description 
45 
Bit address, Single point command 
46 
Bit address, Double point command 
47 
Byte address, Regulating step point command 
48 
Word address, Setpoint normalized point 
command 
49 
Word address, Setpoint scaled point command 
50 
Double-Word address, Setpoint short float point 
command 
51 
Double-Word address, Bitstring (32-bits) point 
command 
100 
*Word address, Group interrogation command  
101 
*Word address, Counter interrogation command  
102 
*Word address, Read command 
103 
*Word address, Clock synchronization 
command 
105 
*Word address, Reset process command 
107 
*Word address, Test command (IEC-870-5-104 
type) 
110 
Word address, Normalized measured value 
111 
Word address, Scaled measured value 
112 
Float (double-word), Short float value  
113 
*Word address, Activation command 
*Word address = Value only used to signal 
when to send event (Enable Code = 2) 
Poll Interval 
1 to 65535 
This parameter is used if the Enable Code field 
is set to a value of 1. Delay (in seconds) to 
execute this command since its last execution. 
To be used if this command is to be executed 
every X seconds. 
Session Index 
0 to 3 
This parameter is utilized to associate the 
command with one of the sessions defined for 
the module. 
Sector Index 
0 to 1 
This parameter is used to associate the 
command with the proper sector of the selected 
session.  
ProSoft Technology, Inc.  Page 69 of 136 