Use Override Flag 
0=Use value in database for value 
512=Use override value for state 
Example - Enabling a Data Type 45 Single Point Value with: 
Single Point value: 1 (On) 
Qualifier Code:  4 (Short pulse duration) 
Select/Execute: 0 (Direct execution without Select) 
Use Override Flag: 512 (Use override value for state) 
1 + 4 + 0 + 512 = 517 
A value of ‘517’ would need to be entered in the Qualifier Parameter for this 
command. 
Data Type 
Description 
48 
Word address, Setpoint normalized point command 
49 
Word address, Setpoint scaled point command 
50 
Double-Word address, Setpoint short float point command 
The following parameter applies to each Data Type (48, 49, 50) 
Qualifier Code 
0=Direct execution without select 
1=Select executed followed by  
execute 
2=Deselect command 
Example – Each of the Setpoint Command Data Types (48, 49, 50) can be 
executed with a value of 0, 1, or 2. 
Data Type 
Description 
Qualifier Parameter 
51 
Double-Word address, Bitstring (32-
bits) point command 
No Qualifier used 