7.1.2  Primary and Standby Controllers 
The Primary controller executes the application program, controls the remote I/O, 
and updates the Standby controller after every scan (program cycle). If the 
Primary controller fails, the Standby controller takes control within one scan. To 
determine if the Primary controller failed note controller’s status displayed in the 
HE CPU LCD screen and the RIO Head’s status displayed by the RIO Head’s 
LEDs.  
The Standby controller does not execute the full application program but only the 
first section, and the Standby controller does not control the remote I/O but 
checks out the availability of the Modicon Quantum Hot Standby with Unity 
equipment. 
Note: For additional information on Quantum Hot Standby support, refer to the Unity Pro Hot 
Standby User Guide. 