User manual
Hot Standby Support  49TPTQ-104C ♦ 48TQuantum Platform 
12TUser Manual  47TIEC 60870-5-104 Client 
%SW60.3: Setting this bit = 0 will force the Standby PLC offline if a logic 
mismatch is detected. Logic mismatch is defined as either the MID, LID or CID 
being different on Primary and Standby sides. Setting this bit = 1 will allow the 
Standby PLC to continue to operate normally even if the MID is different on the 
Primary and Standby.  
%SW60.4: Setting this bit = 1 allows the executive to upgrade on the Standby 
without having to stop the application. This means the Hot Standby system is 
allowed to operate with different versions of the OS running on the Primary and 
Standby. This option is provided to allow upgrades to be done without shutting 
down the process. Clearly, the Standby PLC must be stopped to do the executive 
upgrade, but it will be able to operate as a valid Standby when started again.  
%SW60.5: Setting this bit = 1 commands the standby station to initiate an 
application transfer. That function is not required in UNITY V1.  
%SW60.8: If this bit is set = 1 the Modbus address on port 1 will be swapped 
when a switchover occurs. Swapping means to change address by ± 128 to keep 
the address in the range of 1 to 247. The purpose of this is to allow the P-unit of 
an HMI to always use the same address to connect to the Primary or 
Standby/Offline PLC.  
PLC HSBY Status Register 
The Status Register provides user information relative to the state of the two 
PLCs in the Hot Standby system. The Status Register is %SW61. 
Both the Primary and Standby/Offline PLCs have their own copies of the Status 
register. The Status register is not transferred from Primary to Standby each 
scan. Each PLC must maintain its local Status Register based on the regular 
communication between the two PLCs. 
The following illustration identifies the operating options provided by the 
Command Register. 
%SW61 Hot Standby Status Register 
The following gives additional detail on the various parts of the Status Register. 
Page 90 of 136  ProSoft Technology, Inc. 
  March 4, 2013 










