User manual
49TPTQ-104C ♦ 48TQuantum Platform  Hot Standby Support 
47TIEC 60870-5-104 Client 
  12TUser Manual 
%SW61.0 to 3: These bits display the state of the local and remote Hot Standby 
PLCs. 
%SW61.4: This bit is set = 1 whenever a logic mismatch is detected between the 
Primary and Standby PLCs. This means that either the MID, CID or LID is 
different on the two PLCs. Under this condition, if bit 13 of the Command 
Register is set = 0, bit 1 of the Status Register will be set = 1.  
%SW61.5: This bit identifies the order reported by the Copro at start time 
depends on the range of the MAC addresses.  
  If the A/B designation is A, then bit 5 will be set = 0. 
  If the A/B designation is B, then bit 5 will be set = 1. 
%SW61.14: If set = 1 it indicates that a logic mismatch has been detected that 
disallows Unlocated Variables to be transferred from Primary to Standby. This 
feature was canceled for UNITY V1.1 because it was determined that a 
switchover with a partial application context posed too great a hazard. 
%SW61.15: If set = 1 it indicates that the Copro device is set up correctly and 
working. 