User manual
PTQ-PDPMV1 ♦ Quantum Platform  Hot Standby Support 
PROFIBUS DP Master Network Interface Module for Quantum  User Manual 
ProSoft Technology, Inc.  Page 203 of 306 
August 12, 2014 
Quantum 
Address 
(Example) 
Unity 
Address 
(Example) 
Word 
Offset 
Name 
Description 
1061 
%IW1061 
61 
Low byte: HSBY 
Local Status - from 
PROFIBUS 
interface 
High byte: HSBY 
Local number of 
slaves - from 
PROFIBUS 
interface 
High Byte 
Low Byte 
16 
8 
7 
0 
H
S 
- 
- 
O
D 
D
B 
C
E 
S
O 
P
A 
Bit 
Explanation 
HS 
This bit indicates if the Hot Standby 
functionality is enabled. 
0 - HSBY disabled. Module operates as 
stand-alone Master or HSBY state equals 
"Not connected". 
1 - HSBY enabled 
1062 
%IW1062 
62 
HSBY Message 
length - from UDP 
HSBY Server 
See explanation of bits OD, DB, CE, SO and PA in chart 
for address 1060. 
1063 
%IW1063 
63 
Low byte: HSBY 
Passive Status - 
from UDP HSBY 
Server 
High byte: HSBY 
Passive number of 
slaves Message 
length - from UDP 
HSBY Server 
Refer to word 60 for explanation. This is a backup word 
derived from Ethernet UDP messaging 
1064 to 1165 
%IW1064 to 
%IW1165 
64 to 
65 
HSBY Passive 
PROFIBUS CRC32 
- from UDP HSBY 
Server 
CRC32 checksum for PROFIBUS Master configuration 
downloaded from configuration utility via UDP 
1066 to 1167 
%IW1066 to 
%IW1167 
66 to 
67 
HSBY Passive User 
Cfg CRC32 - from 
UDP HSBY Server 
PTQ-PDPMV1 module configuration checksum for 
module configuration downloaded from configuration 
utility via UDP 
HSBY Input Status Data Word Details 
Quantum Address 
(Example) 
Unity Address 
(Example) 
Relative Word 
Offset 
Description 
1060  
%IW1060 
60 
Remote HSBY Master Status data and number 
of slaves seen by this Master 
1061 
%IW1061 
61 
Local HSBY Master Status data and number of 
slaves seen by this Master 
Word Offset 60 HSBY Local (Active) Master Status Data 
HSBY Active # of Slaves (High byte) 
HSBY Active Status (Low byte) 
15 
8 
7 
0 