7.3.6  Unsupported Functions 
  When the Master module operates as a passive HSBY Master, the following 
mailboxes are not allowed and will be rejected with "Fault information code" 
0x00FD. 
o  FB_APPL_SET_SLAVE_MODE 
o  FB_APPL_GET_MASTER_DIAG 
o  FB_APPL_GET_SLAVE_DIAG (internal request) 
o  FB_APPL_MSAC1_PROFID_V3_PARAM 
  When the Master module operates as HSBY Master (passive or active), 
"Class 2 Master only" mode is not allowed. Refer to FB_INIT (special 
functions, bit 5). 
7.3.7  ProSoft Configuration Builder (PCB) HSBY Option 
Functionality 
ProSoft Configuration Builder is required to set up, control, and identify matched 
Primary/Standby HSBY PTQ-PDPMV1 module sets. 
Considerations should be identified for uploading and downloading of module 
configuration data as if the dual modules were a single module, whereas upon 
downloading the configuration files, files are sent to both PTQ modules 
automatically. 
The PCB will not be required to be concerned with Primary or Standby initially. 
However, the PCB will be required to know which module is Primary in order to 
perform accurate online monitoring (Standby Master modules will not be 
communicating with the slave devices). 
A new icon is created to indicate the PROFIBUS configuration is in Hot Standby 
mode. The icon is displayed as a double PTQ module as shown in the following 
illustration. 