User manual
Configuring the Module  PTQ-PDPMV1 ♦ Quantum Platform 
User Manual  PROFIBUS DP Master Network Interface Module for Quantum 
Page 28 of 306  ProSoft Technology, Inc. 
  August 12, 2014 
The Input Start Register address refers to the 3x (%IW) location in the 
processor’s State RAM and the Output Start Register refers to the 4x (%MW) 
location of State RAM. You can view State RAM information in Unity XL Pro. 
A common mistake is to assume that because the Input Start Register parameter 
starts at address 301000, then the PROFIBUS data associated with the slaves 
will also start at the same register. As the diagram above shows, the Input 
PROFIBUS Data would start at address 301223 for this example. 
Important: The Input and Output Start Register parameters define the start registers for the input 
and output blocks that are transferred between the processor and the module. The PROFIBUS I/O 
associated to the slaves is part of these blocks. Refer to PTQ Input and Output Data Blocks (page 
251) for a description. Each block contains status, PROFIBUS data, and Mailbox/Slave 
diagnostics, if chosen. 
Input Start Register 
The Input Start Register address refers to the 3x (%IW) location in the 
processor’s State RAM. You can view State RAM information in Unity XL Pro. 
Output Start Register 
The Output Start Register refers to the 4x (%MW) location of State RAM. You 
can view State RAM information in Unity XL Pro. 
Input Byte Swap 
Swap bytes in input image (YES or NO). The default value is NO. 
This is a user-configured flag to indicate if input data is swapped before being 
placed in the input image for the controller. If the parameter is set to 0, no 
swapping occurs. If it is not 0, then bytes are swapped. 
For more information on byte swapping, please refer to Status Data in the Input 
Data Block (page 256). 
Output Byte Swap 
Swap bytes in output image (YES or NO). The default value is NO.  
This is a user-configured flag to indicate if output data is swapped after being 
received from the controller. If the parameter is set to 0, no swapping occurs. If it 
is not 0, then bytes are swapped. 
Mailbox Messaging 
Use mailbox messaging over the backplane (Y or N with Y=default). 
For this example, leave the setting at its default. For more information on the 
effect of this setting, please refer to Mailbox Messaging (page 151). 










