Operating instructions
PTQ-MCM ♦ Quantum / Unity Platform  Reference 
Modbus Communication Module 
Page 116 of 139  ProSoft Technology, Inc. 
April 29, 2008 
The following table is a sample read input status request to read inputs 10197 to 
10218 from slave number 11. 
Adr  Func  Data Start Pt Hi  Data Start Pt Lo  Data #of Pts Hi  Data #of Pts 
Lo 
Error Check Field 
11 02 00  C4  00 16 CRC 
Response 
An example response to Read input status is as shown in Figure C4. The data is 
packed one bit for each input. The response includes the slave address, function 
code, quantity of data characters, the data characters, and error checking. Data 
will be packed with one bit for each input (1=ON, 0=OFF). The lower order bit of 
the first character contains the addressed input, and the remainder follow. For 
input quantities that are not even multiples of eight, the last characters will be 
filled in with zeros at high order end. The quantity of data characters is always 
specified as a quantity of RTU characters, that is, the number is the same 
whether RTU or ASCII is used. 
Because the slave interface device is serviced at the end of a controller's scan, 
data will reflect input status at the end of the scan. Some slaves will limit the 
quantity of inputs provided each scan; thus, for large coil quantities, multiple PC 
transactions must be made using coil status for sequential scans. 
Adr Func Byte 
Count 
Data Discrete 
Input 10197 to 
10204 
Data Discrete 
Input 10205 to 
10212 
Data Discrete 
Input 10213 to 
10218 
Error Check 
Field 
11 02 03 AC DB 35  CRC 
The status of inputs 10197 to 10204 is shown as AC (HEX) = 10101 1100 
(binary). Reading left to right, this show that inputs 10204, 10202, and 10199 are 
all on. The other input data bytes are decoded similar. 
Due to the quantity of input statuses requested, the last data field which is shown 
as 35 HEX = 0011 0101 (binary) contains the status of only 6 inputs (10213 to 
102180) instead of 8 inputs. The two left-most bits are provided as zeros to fill 
the 8-bit format. 
8.6.3  Read Holding Registers (Function Code 03) 
Query 
Read holding registers (03) allows the user to obtain the binary contents of 
holding registers 4xxxx in the addressed slave. The registers can store the 
numerical values of associated timers and counters which can be driven to 
external devices. The addressing allows up to 125 registers to obtained at each 
request; however, the specific slave device may have restriction that lower this 
maximum quantity. The registers are numbered form zero (40001 = zero, 40002 
= one, etc.). The broadcast mode is not allowed. 
The example below reads registers 40108 through 40110 from slave 584 number 
11. 
Adr  Func  Data Start Reg Hi  Data Start Reg Lo  Data #of Regs Hi  Data #of Regs Lo  Error Check Field 
11 03 00 6B  00 03 CRC 










