Hold Offset 
0 to 4999 
This parameter specifies the offset address in the internal Modbus database that 
is to be used with network requests for Modbus function 3, 6, or 16 commands. 
For example, if a value of 50 is entered, a request for address 0 will correspond 
to the register 50 in the database. 
Command Count 
0 to 100 
This parameter specifies the number of commands to be processed by the 
Modbus master port. 
Min Cmd Delay 
0 to 65535 
This parameter specifies the number of milliseconds to wait between issuing 
each command. This delay value is not applied to retries. 
Cmd Err Pointer 
-1 to 3995 
This parameter sets the address in the internal Modbus database where the 
command error will be placed. If the value is set to -1, the data will not be 
transferred to the database. The valid range of values for this parameter is -1 to 
4999. For example, if this parameter is configured for 1000, the command errors 
will be copied to the database as follows: 
1000: error code for command 0 
1001: error code for command 1 
etc. 
An error code of 0 means that the command was successfully sent (no error). 
Refer to Error Status Table for the command error code listings. 
Response Timeout 
Response Timeout : 0 #Response timeout for command (Master) 
This parameter represents the message response timeout period in 1-millisecond 
increments. This is the time that a port configured as a master will wait before 
transmitting a command if no response is received from the addressed slave. 
The value is set depending upon the communication network used and the 
expected response time of the slowest device in the network. 