Operating instructions
Diagnostics and Troubleshooting  PTQ-MCM ♦ Quantum / Unity Platform 
  Modbus Communication Module 
ProSoft Technology, Inc.  Page 89 of 139 
April 29, 2008 
Important: When in analyzer mode, program execution will slow down. Only use this tool during a 
troubleshooting session. Before disconnecting from the Config/Debug port, please press [S] to stop 
the data analyzer, and then press [M] to return to the main menu. This action will allow the module 
to resume its normal high speed operating mode. 
Returning to the Main Menu 
Press [M] to return to the Main Menu. 
7.1.7 Data Analyzer Tips 
From the main menu, press [A] for the "Data Analyzer". You should see the 
following text appear on the screen: 
After the "Data Analyzer" mode has been selected, press [?] to view the Data 
Analyzer menu. You will see the following menu: 
From this menu, you can select the "Port", the "format", and the "ticks" that you 
can display the data in. 
For most applications, HEX is the best format to view the data, and this does 
include ASCII based messages (because some characters will not display on 
HyperTerminal and by capturing the data in HEX, we can figure out what the 
corresponding ASCII characters are supposed to be). 
The Tick value is a timing mark. The module will print a _TT for every xx 
milliseconds of no data on the line. Usually 10milliseconds is the best value to 
start with. 