User manual
Reference  PTQ-104S Rev2 ♦ Quantum Platform 
User Manual  IEC 60870-5-104 Server for Quantum 
Page 166 of 195  ProSoft Technology, Inc. 
  February 22, 2013 
The following illustration shows how these parameters are implemented: 
If a database bit address (1 to 64000) is present, the application may consider 
the point with an invalid flag if the previous logic checks the IV bit as 1 during 
consecutive IV Check Delay scans. The IV bits would have to be reset to 0 to set 
the point to valid state. 
The IV DB bit defined for each point can be unique, or many points may share 
the same bit. The last case could be used when the all points on an I/O module 
are to be considered as one set. In this case only a single bit is required. For a 
point that is the result of a computation, the valid quality state could be set for 
each point individually. 