FIRE DETECTION CONTROL PANEL OPERATING & MAINTENANCE MANUAL An ISO 9001 Registered Company APPROVED
IMPORTANT SERVICE NOTICE When requesting service assistance, or to order parts for this control panel, you are required to provide the Model Number, Drawing Number and Serial Number. This product information is recorded on the Panel Identification Label located inside the control panel. Please have this information available before calling your Authorized Protectowire Distributor or the Factory.
60 Washington Street, Pembroke, MA 02359-1833 USA Tel. (781) 826-3878 Fax (781) 826-2045 Visit us on the World Wide Web at: www.protectowire.
Table of Contents Page No. Notice 3 SYSTEM SPECIFICATIONS, INSTALLATION AND OPERATION FS2000 Series Control Panel Information and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 Standard Enclosure Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 LTi2X Enclosure Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents (continued) OPTION Page No. “H” Intrinsic Safety Barrier for Special Hazard Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 “H” Intrinsic Safety Barrier Field Wiring Illustration (IL-1008) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 “K” Intrinsic Safety DC Isolator for Special Hazard Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notice Testing and maintenance of system controls shall be performed by competent, qualified personnel having jurisdiction over this protective signaling system. This system may contain detection zones which are assigned to trip release solenoids and/or equipment shutdown. As a deterrent to accidental activation of the release system, the control card module for systems so equipped does not have a system test (alarm simulate) button.
FS2000 Series Fire Detection Deluge/Preaction Control Panel Information and Specifications The FS2000 Series of multiple zone fire protection panels is the latest in fire protection from The Protectowire Company, Inc.
FS2000 Series Fire Detection Deluge/Preaction Control Panel Information and Specifications (continued) INITIATING CIRCUITS Class A (NFPA Style D)/Class B (NFPA Style A and B) Voltage Standby 22VDC nominal, power limited Current to ensure alarm 15mA (1K ohm loop resistance minimum) Short circuit current 35mA Supervision current 4.5mA End-of-line resistor 4.7K ohm 1 /2 watt (Class B only) Maximum feed cable 100 ohms.
FS2000 Standard Enclosure Dimensions (all dimensions in inches) Enclosure Back Box Dimension Reference Table TYPE A B C D E F ROWS COLUMNS SPACES EN2 17” 21” 4.75” 15” 19” 6” 1 2 2 EN4 31” 21” 4.75” 29” 19” 6” 2 2 4 EN6 31” 26” 4.75” 29” 24” N/A 2 3 6 EN9 42” 26” 4.75” 40” 24” N/A 3 3 9 EN12 53” 26” 4.75” 51” 24” 20” 4 3 12 EN15 64” 26” 4.
FS2000 LTi2X Enclosure Dimensions (all dimensions in inches) A D Enclosure Dimension Reference Table TYPE A B C D E ROWS COLUMNS SPACES LTi2X 17.5” 19.5” 9” 12” 18.85” 2 1 2 Note: Enclosure shown represents the LTi2X only. For LTi4 - LTi9 dimensions reference the LTi4 -LTi9 dimensions page of this manual. Caution: Do not drill through the top of the enclosure for conduit entry. Metal filings and/or water entry from conduit system will damage system components and voids factory warranty.
FS2000 LTi4 - LTi9 Enclosure Dimensions (all dimensions in inches) COLUMNS A D Enclosure Dimension Reference Table TYPE A B C D E ROWS COLUMNS SPACES LTi4 35.25” 24” 6.85” 34” 18” 2 2 4 LTi6 35.25” 29” 6.85” 34” 23” 2 3 6 LTi9 46.25” 29” 6.85” 45” 23” 3 3 9 Note: Enclosure shown represents the LTi4, 6 and 9 only. For LTi2X dimensions reference the LTi2X dimensions page of this manual. Caution: Do not drill through the top of the enclosure for conduit entry.
FS2000 Series Alarm Circuit Installation Guide DS-9066A Issued 3-1-05 Alarm Notification Appliance Circuit Wire Size Estimator To ensure that all alarm notification appliance circuits will be supplied with adequate power to operate, it is necessary to use the correct size feed cable for the distance and current requirement of each circuit. Follow the steps below to calculate the correct wire size for your application. The calculations are based on a maximum line loss (voltage drop) of 2 volts. 1.
FS2000 Series Fire Alarm Control Panel Battery Size Calculation Sheet Use this form to calculate the required battery size for your system. You must first determine the duration the panel will need to function on batteries in hours. The installation wiring diagram for your system includes a factory calculated battery size in the specification section. This calculation is based on a 24-hour backup period for non-releasing systems and a 90 hour backup period for systems with a solenoid releasing module.
FS2000 Series Fire Alarm Control Panel Typical Panel Wire Routing Detail DS-9079B When bringing field wires to and from the control panel you must maintain segregation between Power Limited and Non-Power Limited wiring. Use the illustration below as a guideline for routing wire within the system enclosure. Also reference the field wiring sections of this manual to determine which field connections are Power Limited and which are Non-Power Limited.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation Test and Maintenance Installation and System Power-Up. 1. Carefully unpack the system and inspect for any visible damage from shipping. 2. Mount the system in a clean, easily accessible, stable area with four (4) 1/4” screws. The system enclosure should be mounted to allow clear visibility of the systems control indicators and easy access to the systems control switches. 3.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation, Test and Maintenance Testing and Maintenance Quarterly testing is advised to help ensure system controls are functioning properly. Testing should be performed by competent personnel having jurisdiction over the protective signaling system. The following instructions should be observed in conjunction with the System Operational Outline contained in this manual when testing this equipment. 1.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation Test and Maintenance Operational Outline: 1. Normal Standby Condition a) “AC ON” Indicator (Green) illuminated. 2. Power Supervision AC power source failure: a) “AC ON” Indicator (Green) OFF. b) System trouble buzzer ON (Pulsing) - Press “SUP./TRO. SIL.” button to silence. c) “SYS. TRO.” Indicator (Yellow) Flashing. d) Restore AC power to resume standby condition. DC power source failure: a) “SYSTEM. TROUBLE / SUP.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation Test and Maintenance Operational Outline Continued: 6. Ground Fault Detection Circuit (Not available with Option “H”) When undesirable current flows to ground from the system DC power supply, either positive or negative: a) “SYSTEM TROUBLE / SUP” Indicator (Yellow) Flashing. b) “GND. FAULT” Indicator (Yellow) ON. c) System trouble buzzer ON (Pulsing) - Press “SUP / TRO. SIL.” button to silence.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation Test and Maintenance Detection Circuits Ground Fault Alarm Notification Appliance Circuits Standby Power Primary Basic Troubleshooting Guide for The FS2000 Series Fire Alarm Control Panel Indicator Status Fault Condition Course of Action Alternate Action “A.C. ON” Indicator OUT “SYS. TROUBLE / SUP.
Continued from previous page FS2000 Series Fire Detection Preaction/Deluge Control Panel Operation Installation, Test and Maintenance Alarm Notification Appliance Circuits Solenoid Release Detection Circuits Basic Troubleshooting Guide for The FS2000 Series Fire Alarm Control Panel Indicator Status Fault Condition Course of Action Alternate Action “A.C. ON” Indicator OUT “SYS. ALARM” Indicator ON Zone “ALARM” Indicator ON Short in zone circuit field wiring or initiating device in alarm i.e.
FS2000 Series Fire Detection Preaction/Deluge Control Panel Part Replacement Instructions DS-9038 Rev. B Initial Steps 1. 2. 3. 4. 5. Notify the applicable local fire department and/or alarm receiving station that the system is being serviced. Inform all personnel in the facility that testing is in progress, from the start of servicing to its completion. Reference the systems Installation Wiring Diagram (IWD) for specific connection and component information. Disconnect any and all auxiliary alarm devices.
Main Board - MB-91A Sys. Test feature is available on special orders only and is not provided on systems with solenoid releasing. ELR-4.7K 1/2 W ELR-4.7K 1/2 W MAIN BOARD DISPLAY PANEL MAIN BOARD MB-91A/M PROGRAMMABLE TROUBLE CONTACTS PROGRAMMABLE TROUBLE CONTACTS PROGRAMMABLE SUPERVISORY CONTACTS STANDARD CLASS B ALARM NOTIFICATION APPLIANCE CIRCUITS (2) N.O. / N.C. COM. N.O. / N.C. COM. N.O. / N.C. COM. COM. SILENCEABLE ALARM CONTACTS N.C. N.O. ELR-4.7K 1/2 W ELR-4.
Main Board - MB-91A/M MB-91A Variations MB-91A MB-91A/M Standard main board supporting non-metered Class A/B detection circuits Metered main board supporting Class A/B detection circuits with Alarm point location meter System Control Switches SYS. TEST SYS. RST. AL. SIL. TRO. SIL. System test button: Press and hold for a minimum of 3 seconds. This simulates an ALARM condition in all detection and supervisory zones.
Main Board MB-91A/M - Field Wiring Common Trouble Contacts 1 amp @ 24 VDC, Resistive load 2 sets available. See Option “S” page for silencable & nonsilenceable operation Common Supervisory 1 amp @ 24 VDC, Resistive load 1 set available Contacts (non-silenceable) Common Alarm 3 amps @ 30 VDC, Resistive load 1 set available Contacts (silenceable) Notification Appliance 2 amps per circuit 3 amps maximum combined @ 19 - 32.
Main Board MB-91A/M Field Wiring Initiating Device Circuits Class A (NFPA Style D)/Class B (NFPA Style A and B) Voltage Standby 22VDC nominal, power limited Current to ensure alarm 15 mA (1K ohm loop resistance minimum) Short circuit current 35 mA Supervision current 4.5 mA End-of-line resistor 4.7 K ohm 1/2 Watt (Class B only) Maximum feed cable resistance 100 ohms. Feed cable may consist of any combination of Protectowire or copper feed Ground Fault Impedance rating Less than 2.
4-Wire Detector Power Supervision Description - Supervision of power to 4-wire detectors is necessary to ensure their operation. Supervision is accomplished by installing a Power Supervisory Relay (PSR), Model PSR-2040 or its equivalent after the last detector. The relay contacts are normally closed when power is present at the last detector. These contacts are wired in series with the supervised detection circuit.
Expander Board - EB-91A/M The zone expander board can accommodate up to (4) initiating device zones. Two zone cards per expander board with (2) initiating device zones per card. Zones can be implemented as Class A/B detection, waterflow or switch supervisory circuits depending on the card type being utilized. It can also accommodate (2) alarm notification appliance cards (AE-91) with (1) notification appliance circuit per card.
Expander Board - EB-91A/M The zone expander board can accommodate up to (4) initiating device zones. Two zone cards per expander board with (2) initiating device zones per card. Zones can be implemented as Class A/B detection, waterflow or switch supervisory circuits depending on the jumper configuration of the ZC-91A card. The Expander Board can also accommodate (2) Alarm B Notification Control cards (AE-91) with (1) Notification Appliance circuit per card.
Expander Board EB-91A/M Field Wiring Initiating Device Circuits Class A (NFPA Style D)/Class B (NFPA Style A and B) Voltage Standby Current to insure alarm Short circuit current Supervision current End-of-line resistor Maximum feed cable resistance 22VDC nominal, power limited 15mA (1K ohm loop resistance minimum) 35mA 4.5mA ELR-4.7K, 1/2 Watt (Class B only) 100 ohms.
Control Card Module - CC-91A The Control Card CC-91A provides system controls and indicator for the FS2000 Series system. This card plugs into the Main Board MB-91A/M printed circuit board left side card slot. System control switches, lamp indicators and signal monitoring are managed with this module. Plug-in design allows for quick replacement during field repair. Used in conjunction with the Main Board (MB-91A). Standard control card module is designated as CC-91ANT.
Control Card Module - CC-91A The Control Card CC-91A provides system control and indicators for the FS2000 Series system. This card plugs into the Main Board MB-91A/M printed circuit board left side card slot. System control switches, lamp indicators and signal monitoring are managed with this module. Plug-in design allows for quick replacement during field repair. Used in conjunction with the Main Board (MB-91A). Standard control card module is designated as CC-91ANT.
Zone Card Modules - ZC-91A (For Detection Applications) DESCRIPTION: The zone card ZC-91A provides two Class A/B alarm initiating device circuits configured for alarm monitoring. Each zone is individually equipped with alarm (red) and trouble (yellow) indicators for immediate status identification.
Zone Card Module - ZC-91A (For Detection Applications) DESCRIPTION: The zone card ZC-91A provides two Class A/B alarm initiating device circuits configured for alarm monitoring. Each zone is individually equipped with alarm (red) and trouble (yellow) indicators for immediate status identification.
Option “A” - PDM-1000-2 Protectowire Alarm Point Location Meter PDM-1000-2 DESCRIPTION: The PDM-1000-2 PROTECTOWIRE Digital Alarm Point Location Meter is designed to help locate a heat actuated point on a PROTECTOWIRE linear heat detector circuit. This meter identifies the distance in feet or meters (preset at the factory) along the detector from the start of the run to the actuated point.
Option “C” - NDS-91-16X, 16 Zone Alarm Scanner DESCRIPTION: The NDS-91-16X Sixteen Zone Alarm Scanner identifies the zone number in conjunction with linear alarm point identification of a PROTECTOWIRE heat sensitive cable detection zone. In the automatic (AUTO) scan mode this device continually steps through all active (not bypassed) detection zones until an alarm input signal is received.
Option “D” - Waterflow Detection Card -ZC-91AW The zone card ZC-91AW provides two Class A or Class B alarm initiating device circuits for waterflow detection monitoring. Both waterflow alarm circuits are equipped with alarm and trouble indicators for immediate off normal status identification. The waterflow card must be programmed per jumper settings noted below and plugs into the Main Board MB-91A/M and/or Expander Boards EB-91A/M printed circuit board card slots.
Option “D” - Waterflow Detection Card -ZC-91AW The zone card ZC-91AW provides two Class A or Class B alarm initiating device circuits for waterflow detection monitoring. Both waterflow alarm circuits are equipped with alarm and trouble indicators for immediate off normal status identification. The waterflow card must be programmed per jumper settings noted below and plugs into the Main Board MB-91A/M and/or Expander Boards EB-91A/M printed circuit board card slots.
Option “E” - Switch Supervisory Card - SC-91A DESCRIPTION: The supervisory card SC-91A provides two Class A/B alarm initiating supervisory circuits to recognize the activation of a normally open switches (tamper, low air, temperature, etc.) Each zone is equipped with individual alarm (yellow) and trouble (yellow) LED’s for diagnostic ease. This card plugs into the second edge connector slot of the Main Board (MB-91A) and/or any Expander Board module (EB-91A/M) slot.
Option “F” - Solenoid Release/Initiating device card, RS-1 Description: The RS-1 Solenoid release / initiating device card provides one supervised solenoid output circuit. This circuit electrically energizes the coil of a releasing agent control valve and is equipped with "Trouble" and "Trip" L.E.D. indicators for complete valve supervision and activation monitoring. An on-board auxiliary alarm (release) contact is supplied making remote signaling upon solenoid activation easily implemented.
Solenoid Release/Initiating Device Card Field Wiring, Electrical Specifications & Jumper Settings Electrical Requirements: Electrical - Initiating Device Cirucit Voltage Standby 22VDC Current to Insure Alarm 11mA Less than 1.5K Ohm loop resistance maximum to insure alarm End-of-Line Resistor (detection zone) #1 ELR-4.7K 1/2 Watt, 5% Electrical - Solenoid Release Circuit Voltage Standby 0.87VDC @ 1K Ohm Voltage Alarm 26VDC Current Alarm 0.
Solenoid Release/Initiating Device Card Field Wiring, Electrical Specifications & Jumper Settings Electrical Requirements: Electrical - Initiating Device Circuit Voltage Standby 22VDC Current to Insure Alarm 11mA Less than 1.5 K Ohm loop resistance maximum to insure alarm End-of-Line Resistor ELR-4.7K, 1/2 Watt, 5% FM approved Solenoid Groups Groups A thru K Fuse (F1) used with Star D (Group C valve only #1 4 Amp Slo-Blo Electrical - Solenoid Release Circuit Voltage Standby 0.
Option “H” - Intrinsic Safety Barrier for Special Hazard Applications DESCRIPTION: Some applications of PROTECTOWIRE linear heat detection circuits require energy limiting to prevent explosions in areas classified as hazardous locations. One method used to accomplish this “Intrinsic Safety” is to utilize diode shunt barriers. Diode shunt barriers consist of zener diodes with current limiting resistors which “shunt” excess voltage spikes to ground.
~ 40 ~
Option “k” - Intrinsic Safety DC Isolator for Special Hazard Applications DESCRIPTION: In some hazardous area applications, the loss of ground fault detection in non-safe field circuits is unacceptable. Such cases require the implementation of DC isolators. These devices provide three part isolation between the initiating circuit input, output and power supply circuits of each unit. Also intrinsic safety is provided without the need for special earth grounding which reduces the cost in most installations.
~ 42 ~
Option “L” AND “LL” - Auxiliary Zone Alarm Relays DESCRIPTION: Auxiliary zone alarm signaling relays (AS) are often needed to provide an interface to other systems for annunciation and/or to pilot electrical shutdown. Also, (AS) relays may be used for cross zoning initiating circuits or various panel control functions. Reference the Installation Wiring Diagram (IWD) for specific function of installed relays.
Option “P” - Battery Charger Status Meters DESCRIPTION: An available numerical indication of battery status may be provided with Battery Charger Status Meters. These meters supply an easy-to-read accurate display of both the charger current draw and the charging/standby voltage level. OPERATION: The ammeter continuously displays battery charger current draw. This level may be between 1.250 amps and 0.012 amps (trickle current), depending on the present charge state of the batteries.
Option “R” - Common Alarm Signaling Relay DESCRIPTION: The Common Alarm Signaling (CAS) Relay provides two sets of contacts for interfacing to other control equipment upon the initiation of any alarm condition. This relay is normally non-silenceable but can be field modified to provide silenceable contacts. OPERATION: The relays positive terminal (18/24) is sourced with 24V FWR.
Option “RR” - Auxiliary Relay Module - RB-98 DESCRIPTION: Auxiliary signaling relays are often needed to provide an interface to other systems for annunciation and/or to pilot electrical shutdown. Auxiliary signaling relays may be used for “cross zoning” initiating circuits or other various panel control functions. The RB-98 Relay Module provides (8) individually activated sets of Form “C” contacts in one module. Reference the Installation Wiring Diagram (IWD) for specific function of installed relays.
Option “T” - Class A Alarm Notification Appliance Circuit Adapter DESCRIPTION: The AM-91 Alarm Notification Appliance Circuit Adapter Module converts the two Class B system Alarm Notification Appliance Circuits of the Main Board MB-91 to Class A type circuits. This provides 4 wire alarm notification appliance circuits in lieu of the standard 2 wire circuits. OPERATION: The two wire Class B circuits are wired into the module input terminals.
Option “U” - Alarm Expander Card DESCRIPTION: The AE-91 Alarm Expander Card provides one alarm notification appliance circuit which may be wired in a Class A or Class B configuration (NFPA styles X and Z or W and Y). The module plugs into an expander board (EB-91A) expansion slot and can be factory programmed for general alarm activation or for selective activation by up to (4) individual detection zones.
Option “V” - Zone Voting Module DESCRIPTION: The ZV-91 Zone Voting Module is designed to supply an output signal upon the receipt of multiple zone alarm signals. The standard configuration produces a single output signal after receipt of (2) input signals. The module is also available in a (3) input version. The module can monitor up to sixteen inputs and provides (4) individual outputs for system function activation.
FS2000 Series Control Panel Preaction Double Interlock Deluge Cross Zoning Applications Data Sheet Double Interlock Sprinkler Systems are designed to prevent accidental release of water. When the solenoid is energized, depressurization of the air filled pipes (loss of air) is required to obtain water at the sprinkler heads. This beneficial feature becomes a concern when the system is operating under battery backup power.
Option “X” - Dual Temp. Zone Card Module - ZC-95 ELECTRICAL/SPECIFICATIONS Inherent Current Supervisory Voltage Supervisory Current Maximum Alarm current Current to insure alarm Maximum loop resistance LHD per zone 30 mA per card 21.5 VDC 4.5 mA per circuit 35 mA per circuit 12 mA per circuit 1000 ohms per circuit 5000 ft Max. LHD = Linear Heat Detector ZC-95 DISPLAY PANEL ZC-95 DESCRIPTION: Provides two independent detection zones.
Option “X” - Dual Temperature Zone Card - ZC-95 Field wiring for Main Board (MB-91) and Expander Board (EB-91) PROTECTOWIRE TYPE "TRI" POWER LIMITED DUAL TEMPERATURE THREE (3) WIRE LINEAR HEAT DETECTION CIRCUITS (2) COMMON (BLACK) ALARM (CLEAR WIRE) TRIP @ 200° F PRE-ALARM (RED/PINK WIRE) TRIP @ 155° F ALARM TEST PRE-ALARM TEST END OF LINE RESISTOR BOX W/ TEST SWITCHES FEED WIRES 18 AWG MIN. ZONE 1 ELR'S 4.7K 1/2W PROTECTOWIRE Length: 5000 FT Max.
Option “Y” - Power Conditioning Module DESCRIPTION: The PS-95 Power Conditioning Module is designed to provide filtered, regulated DC power from a full wave rectified source (FWR). The module can provide 26 VDC power to devices such as UV/IR detectors, Gas Detectors, Fiber Optic Controllers and Four Wire Smoke Detectors. This module also provides both resettable or non resettable outputs, either may be utilized depending on what the application requires.
Option “Z” - External key Operated Switches DESCRIPTION: Option “Z” consists of four (4) externally mounted key operated switches. These switches are used to duplicate the main control functions normally operated by the push buttons mounted on the Control Card (CC-91) located inside the FS2000 system enclosure. System function provided by the external key switches are “System Reset,” “Alarm Silence,” “Trouble/Supervisory Silence” and “Lamp Test.
Preaction Manual Release Station DESCRIPTION: When solenoid releasing is employed, a means of manually activating the solenoid must also be provided for each release circuit as required by Underwriters Laboratories. The SG-32SK1 non-coded double action manual release station can provide this capability. The SG-32SK1 “Fire System Release” manual station is normally installed across the initiating detection zone configured to activate a solenoid releasing valve.
Release/Sw. Supervisory Board Display FS2000 Series Fire Alarm Control Panel Instructions Main Board Display Expander Board Display LOCAL SERVICE REPRESENTATIVE Name: Address: Phone #: System Control Switches SYS. TEST System test button: Press and hold for a minimum of 3 seconds. This simulates an ALARM condition in all detection and supervisory zones. This test feature is applicable to systems without solenoid releasing (Option G) only. SYS.
APPENDIX A The following Smoke Detectors/ Solenoids / Notification Appliance Circuits (NAC’s) are all approved by UL for use in the FS2000 panel Unless DET. MODEL IDENTIFIER BASE MODEL IDENTIFIER SLR-24V HD-3 NS6-220 HB-3 SLR-24H HD-3 NS6-220 HB-3 SIJ-24 HD-3 NS6-220 HB-3 Compatible 24 Volt Solenoids: Solenoid Power/ Current FM Solenoid Group Size NPS 16.8 WATTS, 700mA B 1/2 in. NPS, 1/2 in orifice 10.6 WATTS, 440mA D 1/2 in. NPS, 1/2 in orifice 11 WATTS, 458mA A 1/2 in.
APPENDIX A (continued) The following 24 Volts DC Notification Appliancel Circuits (NACs) are all UL approved for use on the FS2000 Fire Control Panel. Note Wheelock Synch module DSM-12/24-R must be used for synchronization of Horn / Strobes. * - Indicates Field Selectable Device Important: consult manufacture cut-sheet for actual current draw NAC type Model / Series Average Current Vibartone Horn 450 LP3 Series LP6 LP1 AV1ST AV1 LP7 .25 Amps .25 Amps .25 Amps .08 Amps .39 Amps .98 Amps .
APPENDIX A (continued) Important: consult manufacture cut-sheet for actual current draw * - Indicates Field Selectable Device NAC type Model / Series * RSD24-75110 * RSD24-153075 Strobe Light Retrofit * RSB24-153075 Amesco .250 Amps .114 Amps RSD24-110 .200 Amps Temporal Module TMP1-3A .025 Amps Synchronization Module SMS1-3A .009 Amps Conical Strobe Light SL-5 Series .25 Amps Mini Horn * MIZ Series .017 Amps * AMT Series .098 Amps MB Series .
The Protectowire Company, Inc. 60 Washington Street, Pembroke, MA 02359 U.S.A. n p:781-826-3878 web: www.protectowire.com n email: pwire@protectowire.