Datasheet

CP10.121, CP10.122
CP-Series
12V, 16A, 192W, SINGLE PHASE INPUT
25.10. OPERATION ON TWO PHASES
The power supply can also be used on two-phases of a three-phase-
system. Such a phase-to-phase connection is allowed as long as the
supplying voltage is below 240V
+10%
.
240V
+10%
max.
L2
L1
L3
L
N
PE
Power Supply
AC
DC
Center
Tap
25.11. USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of
1cm.
Case A Case B Case C
Case D
Enclosure size
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100,
plastic
180x180x165mm
Rittal Typ IP66 Box
PK 9519 100,
plastic
Input voltage 230Vac 230Vac 230Vac 230Vac
Load
12V, 12.8A; (=80%) 12V, 16A; (=100%) 12V, 12.8A; (=80%) 12V, 16A; (=100%)
Temperature inside the box 47.4°C 56.3°C 46.2°C 53.4°C
Temperature outside the box 24.6°C 25.7°C 24.4°C 26.0°C
Temperature rise 22.8K 30.6K 21.8K 27.4K
Aug. 2017 / Rev. 1.3 DS-CP10.121-EN
All parameters are typical values specified at 230Vac, 50Hz input voltage, 12V 16A output, 25°C ambient temperature and
after a 5 minutes run-in time unless otherwise noted.