Datasheet
CP10.121
CP-Series
12V, 16A, SINGLE PHASE INPUT
4. DC-INPUT
DC input nom. DC 110-150V ±20%
DC input range min. 88-187Vdc continuous operation
DC input current typ. 1.9A 110Vdc, at 12V, 16A
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103
Turn-on voltage typ. 80Vdc steady state value
Shut-down voltage typ. 74Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N
a) Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage
the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 11A
peak
7A
peak
11A
peak
at 40°C, cold start
typ. 9A
peak
6A
peak
6A
peak
at 25°C, cold start
typ. 9A
peak
6A
peak
9A
peak
at 40°C, cold start
Inrush energy max.
0.1A²s 0.1A²s 0.4A²s
at 40°C, cold start
Fig. 5-1 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient
Fig. 5-2 Typical turn-on behaviour at nominal
load, 230Vac input and 25°C ambient
50ms/DIV
50ms/DIV
6A
5/26
Input current
2A/DIV
Input current
2A/DIV
6A
Input voltage
250V/DIV
Input voltage
500V/DIV
Output voltage 10V/DIV
Output voltage 10V/DIV
Jun. 2015 / Rev. 1.0 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany