Datasheet

CP10.121
CP-Series
12V, 16A, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Dynamic output current capability,
typ.
Output Voltage
0
020
2
4
6
16V
8
10
12
35
A
105 15 25 30
14
Adjustment
Range
Output Current
Continuous
current
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
2
4
8
16V
10
12
14
80A3216 48 64824405672
6
Adjustment
Range
Output Current
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, preliminary, typ.
Output
Current
0
25A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 108ms 108ms 108ms at 12V, 8A, see Fig. 7-1
min. 81ms 81ms 81ms at 12V, 8A, see Fig. 7-1
typ. 50ms 50ms 50ms at 12V, 16A, see Fig. 7-1
min. 38ms 38ms 38ms at 12V, 16A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
7/26
0
20
40
120ms
90 120 155 190 230Vac
Input Voltage
60
100
Hold-up Time
a) 12V 8A typ.
b) 12V 8A min.
a
b
c) 12V 16A typ.
d) 12V 16A min.
80
c
d
- 5%
Zero Transition
Output
Voltage
Input
Voltage
Hold-up Time
Jun. 2015 / Rev. 1.0 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany