Datasheet

CP10.121
CP-Series
12V, 16A, SINGLE PHASE INPUT
10. EFFICIENCY AND POWER LOSSES
AC 100V AC 120V AC 230V
Efficiency typ. 92.1% 92.8% 94.3% at 12V, 16A
typ. 92.0% 92.7% 94.2% at 12V, 19.2A (Power Boost)
Average efficiency
*)
typ. 91.6% 92.2% 93.3% 25% at 4A, 25% at 8A,
25% at 12A. 25% at 16A
Power losses typ. 0.5W 0.5W 0.6W Shut-down activated
typ. 3.1W 3.0W 2.5W at 12V, 0A
typ. 8.0W 7.8W 6.7W at 12V, 8A
typ. 16.5W 14.9W 11.6W at 12V, 16A
typ. 20.0W 18.1W 13.9W at 12V, 19.2A (Power Boost)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
**) In OFF mode, the unit fulfills the ErP requirements of the European Union.
Fig. 10-1 Efficiency vs. output current at 12V,
typ.
Fig. 10-2 Losses vs. output current at 12V,
typ.
Efficiency
9/26
2 4 6 8 10 12 16 18 20A
89
90
91
92
93
94
95%
Output Current
14
(
a
)
(
b
)
(
c
)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Power Losses
0 2 6 8 12 14 20A
4
0
8
12
16
24W
18
20
4 10 16
Output Current
(
a
)
(
b
)
(
c
)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Fig. 10-3 Efficiency vs. input voltage at 12V,
16A, typ.
Fig. 10-4 Losses vs. input voltage at 12V, 16A,
typ.
Efficiency
120 180 230 264Vac
90
91
92
93
Input Voltage
94
95
96%
100
Power Losses
120 180 230 264Vac
8
10
12
14
Input Voltage
16
18
20W
100
Jun. 2015 / Rev. 1.0 DS-CP10.121-EN
All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany