36V, 6.7A, 240W, SINGLE PHASE INPUT
13. TERMINALS AND WIRING
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Input and output DC-OK-Signal
Type
Screw terminals Push-in terminals
Solid wire Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 AWG 24-16
Wire diameter Max. 2.8mm (including ferrules) Max. 1.6mm (including ferrules)
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-head No 2 Not required
Recommended tightening torque 1Nm, 9lb.in Not applicable
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 13-2.
Fig. 13-1 Daisy chaining of outputs Fig. 13-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25A!
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Aug. 2017 / Rev. 1.1 DS-CP10.361-EN