Datasheet

CP10.361
CP-Series
36V, 6.7A, 240W, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Dynamic output current capability,
typ.
Output Voltage
0
0 7.5
6
12
18
42V
24
30
36
12A4.51.5 3 6 9 10.5
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
6
12
18
42V
24
30
36
30A12618243 9 15 21 27
Adjustment
Range
Output Current
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, typ.
Output
Current
0
9.7A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time Typ. 76ms 76ms 76ms At 36V, 3.35A, see Fig. 7-1
Min. 57ms 57ms 57ms At 36V, 3.35A, see Fig. 7-1
Typ. 38ms 38ms 38ms At 36V, 6.7A, see Fig. 7-1
Min. 28ms 28ms 28ms At 36V, 6.7A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
8/29
0
10
20
30
40
80ms
90 120 155 190 230Vac
Input Voltage
50
60
Hold-up Time
a) 36V 3.35A typ.
b) 36V 3.35A min.
70
a
c) 36V 6.7A typ.
d) 36V 6.7A min.
b
c
d
- 5%
Zero Transition
Output
Voltage
Input
Voltage
Hold-up Time
Aug. 2017 / Rev. 1.1 DS-CP10.361-EN
All parameters are specified at 36V, 6.7A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.