CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series POWER SUPPLY AC 100-240V Wide-range Input Width only 48mm Efficiency up to 95.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series INDEX Page 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Intended Use .......................................................3 Installation Instructions ......................................3 AC-Input...............................................................5 DC-Input...............................................................6 Input Inrush Current ..............
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 1. INTENDED USE This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control, monitoring and measurement equipment or the like. Do not use this device in equipment where malfunction may cause severe personal injury or threaten human life. 2.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5mm can be reduced to zero.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 3. AC-INPUT The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. For suitable DC supply voltages see chapter 4. Nom. AC 100-240V Min. 85-264Vac Continuous operation Min. 264-300Vac Occasionally for maximal 500ms Max. 300Vac Continuous, according to IEC 60664-1 Nom. 50–60Hz ±6% Typ. 82Vac Steady-state value, see Fig. 3-1 Typ. 72Vac Steady-state value, see Fig.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 4. DC-INPUT The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 5. INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Inrush current Max. Typ. Max. Inrush energy AC 100V 15Apeak 12Apeak 1A2s AC 120V 12Apeak 10Apeak 1A2s AC 230V 5.5Apeak 4.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 6. OUTPUT The output provides a SELV/PELV/ES1 rated voltage, which is galvanically isolated from the input voltage. The device is designed to supply any kind of loads, including capacitive and inductive loads.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 2) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3. Fig.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 7. HOLD-UP TIME The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time. Hold-up Time Typ. Min. Typ. Min. Fig. 7-1 Hold-up time vs.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 9. REMOTE ON / OFF FUNCTION This feature is available only for the CP20.241-V1 and allows to switch-off the power supply output with a signal switch or transistor. A link between pin 15 and 16 turns the power supply on. Pin 15 is referenced to the (-) output voltage. 16 Remote ON/OFF 15 The open-loop voltage between pin 16 and pin 15 can be up to 18V.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 10. EFFICIENCY AND POWER LOSSES Average efficiency*) Typ. Typ. Typ. AC 100V 93.6% 93.5% 93.2% AC 120V 94.2% 94.1% 93.8% AC 230V 95.6% 95.5% 95.0% Power losses typ. 0.4W 0.5W 0.9W Typ. Typ. Typ. Typ. 2.5W 16.0W 32.8W 40.0W 2.2W 15.0W 29.6W 36.1W 2.2W 12.5W 22.1W 27.1W Efficiency *) At 24V, 20A At 24V, 24A (Power Boost) 25% at 5A, 25% at 10A, 25% at 15A. 25% at 20A CP20.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 11. FUNCTIONAL DIAGRAM Fig. 11-1 Functional diagram CP20.241, CP20.241-C1, CP20,241-S1, CP20.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 12. FRONT SIDE AND USER ELEMENTS Fig. 12-1 Front side CP20.241, CP20.241-C1 A CP20.241-S1 CP20.241-S2 CP20.241-V1 CP10.242 Input Terminals N, L Line input PE (Protective Earth) input Output Terminals CP20.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 13. CONNECTION TERMINALS The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring. CP20.241, CP20.241-C1, CP20.241-V1, CP20.242 Type Solid wire Stranded wire American Wire Gauge Max. wire diameter (including ferrules) Recommended tightening torque Wire stripping length Screwdriver CP20.241-S1 Type Solid wire Stranded wire American Wire Gauge Max.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 14. LIFETIME EXPECTANCY The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 16. EMC The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments. The output is allowed to be grounded or floating. The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4. Without additional measures to reduce the conducted emissions on the output (e.g.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 17.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 18. SAFETY AND PROTECTION FEATURES Isolation resistance Min. 500MOhm Min. 500MOhm Min. 500MOhm Min. 500MOhm PE resistance Max. 0.1Ohm Output over-voltage protection Typ. Max. 30.5Vdc 32Vdc In case of an internal defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 19. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. The output is insulated to the input by a double or reinforced insulation. Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 20. APPROVALS EC Declaration of Conformity The CE mark indicates conformance with the - RoHS directive - EMC directive, - Low-voltage directive and the - ATEX directive CB Scheme, Information Technology Equipment IEC 60950-1 2nd Edition (except for CP20.242) UL 508 (except for CP20.242) IND. CONT. EQ. UL 60950-1 2nd Edition (except for CP20.242) EN 60079-0, EN 60079-7 ATEX (except for CP20.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 22. PHYSICAL DIMENSIONS AND WEIGHT Width Height Depth Weight DIN-Rail Housing material Installation clearances Penetration protection CP20.241 CP10.241-C1 CP10.242 48mm 1.89’’ 124mm 4.88’’ 127mm 5.0’’ The DIN-rail height must be added to the unit depth to calculate the total required installation depth. 830g / 1.83lb Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 23. ACCESSORIES 23.1. ZM5.WALL – WALL/PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall/panel without utilizing a DIN-Rail and can be mounted without detaching the DIN-rail brackets of the power supply. Fig. 23-1 Isometric view (Picture shows the CP20.241) Fig. 23-3 Isometric view (Picture shows the CP20.241) Fig. 23-2 Isometric view(Picture shows the CP20.241) Fig.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE 23.2. UF20.241 BUFFER MODULE The UF20.241 buffer module is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures or extends the hold-up time after the AC power is turned off. When the power supply provides a sufficient voltage, the buffer module stores energy in the integrated electrolytic capacitors.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 CP-Series 24V, 20A, 480W, SINGLE PHASE 23.5. YR40.245 - REDUNDANCY MODULES The YR40.245 is a 40A single channel redundancy module, which is equipped with a plug connector on the output. The plug connector allows replacing the power supply or the redundancy module while the system is running. The plug connector prevents the output wires from touching and creating a short the load circuit.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24. APPLICATION NOTES 24.1. PEAK CURRENT CAPABILITY The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.2. OUTPUT CIRCUIT BREAKERS Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 24V branches. MCB’s are designed to protect wires and circuits.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.3. CHARGING OF BATTERIES The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are needed in series connection. Instructions for charging batteries: a) Use only matched batteries when putting 12V types in series. b) Ensure that the ambient temperature of the power supply stays below 40°C.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.5. PARALLEL USE TO INCREASE OUTPUT POWER Devices can be paralleled to increase the output power. The output voltage of all power supplies shall be adjusted to the same value (±100mV) in “Single Use” mode with the same load conditions on all units, or the units can be left with the factory settings. After the adjustments, set the unit to “Parallel Use” mode, in order to achieve load sharing.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.6. PARALLEL USE FOR REDUNDANCY Please note that there are variants with built-in redundancy are available in the CP20 series. Check CP20.241-Rx units. 1+1 Redundancy: Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.7. OPERATION ON TWO PHASES Power Supply Ensure that the wire, which is connected to the N-terminal, is appropriately fused. The maximum allowed voltage between a Phase and the PE must be below 300Vac. 240V +10% max. L1 The power supply can also be used on two-phases of a three-phasesystem. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%.
CP20.241, CP20.241-C1, CP20.241-S1, CP20.241-S2, CP20.241-V1, CP20.242 24V, 20A, 480W, SINGLE PHASE CP-Series 24.9. MOUNTING ORIENTATIONS Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation.