15. ENVIRONMENT
Conformal coating yes all pc-boards are conformal coated
Operational temperature
*)
-40°C to +70°C (-40°F to 158°F) continuous operation, reduce output power
according Fig. 15-1 for input voltages below
100Vdc
+70°C to +85°C (185°F to 185°F) for maximal 10 minutes every hour
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 0.08A/V at +70°C or
0.16A/°C at 77Vdc
required for input voltage smaller than 100Vdc
in combination with ambient temperatures
above +60°C (140°F).
Derate linearly between 100Vdc and 77Vdc or
+60°C and +70°C, see Fig. 15-1.
Humidity
**)
5 to 95% r.h. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
IEC 60068-2-6; DC/DC converter in operation
Vibration broadband 1.01grms for 10 minutes; 5-150Hz
***)
IEC 60068-2-64, DC/DC converter in operation;
Tests limits according to EN 61373
Vibration broadband 5.72grms for 300 minutes; 5-150Hz
***)
IEC 60068-2-64, DC/DC converter not in
operation; Tests limits according to EN 61373
Shock 30g 6ms, 20g 11ms, 50g 30ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27; DC/DC converter in operation
Shock 50g 30ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27, DC/DC converter not in
operation; Tests limits according to EN 61373
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating 24W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 15-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Audible noise At load currents below 2A some audible noise will be emitted from the DC/DC converter
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard
orientation. Higher levels allowed when using the wall mounting bracket ZM2.WALL
Fig. 15-1 Output current vs. ambient temp. Fig. 15-2 Output current vs. altitude
Allowed Output Current
0
-40 0 20 40
85°C
3
6
9
12
16.3A
18A
60-20 70
15
A
B
Ambient Temperature
A...100 to 154Vdc, continuous
B... 77 to 100Vdc, continuous
C... for maximal 10 minutes
C
0
0 2000m 4000m
6000m
3
6
9
12
15
18A
16.3A
Allowable Output Current
Altitude
B
C
A
.
.
.
T
a
m
b
<
7
0
°
C
B
.
.
.
T
a
m
b
<
6
0
°
C
C
.
.
.
T
a
m
b
<
5
0
°
C
A
Aug. 2016 / Rev. 1.0 DS-CPS20.241-60-EN
All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/22