Data Sheet

CPS20.241-60
C-Series
24V, 400W, DC/DC CONVERTER
3. AC-INPUT
Do not operate this DC/DC converter with an AC-input voltage. Use the CPS20.241 or CPS20.241-C1 unit instead.
4. DC-INPUT
Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the unit.
Input voltage nom. DC 110V -30%/+40%
Input voltage range 77-154Vdc
66-77Vdc short term for 100ms
Input current typ. 3.87A at 16.3A and 110Vdc input voltage, see Fig. 4-3
Allowed voltage between input
to earth (ground)
max. 375Vdc continuous, IEC 62103
± 600V peak value, allowed for transients
Slew rate for voltage between
input to earth (ground)
max. 1000V/μs
Allowed input ripple voltage max. 15Vpp
3Vpp
50Hz –10kHz
10kHz – 50kHz
Turn-on voltage typ. 77Vdc steady-state value, at ambient temperatures between
-20°C and +70°C, see Fig. 4-1
typ. 85Vdc steady-state value, at -40°C ambient temperature
Shut-down voltage typ. 60Vdc steady-state value, see Fig. 4-1
Start-up delay typ. 900ms see Fig. 4-2
Rise time typ. 85ms at 16.3A constant current load, 0mF load capacitance,
see Fig. 4-2
typ. 130ms at 16.3A constant current load, 20mF load capacitance,
see Fig. 4-2
Turn-on overshoot max. 200mV see Fig. 4-2
External input protection See recommendations in chapter 23.3.
Fig. 4-1 Input voltage range Fig. 4-2 Turn-on behavior, definitions
Turn-on
77V
Rated
input range
max.
500ms
V
IN
P
OUT
375Vdc154V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Aug. 2016 / Rev. 1.0 DS-CPS20.241-60-EN
All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/22