Datasheet

CPS20.361
C-Series
36V, 13.3A, SINGLE PHASE INPUT
13. FRONT SIDE AND USER ELEMENTS
Fig. 13-1 Front side
A
Input Terminals (screw terminals)
N, L Line input
PE (Protective Earth) input
B
Output Terminals (screw terminals, two pins per pole)
+ Positive output
Negative (return) output
C
Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 36.0V
D
DC-OK LED (green)
On, when the output voltage is >90% of the adjusted output voltage
E
DC-OK Relay Contact (quick-connect spring-clamp terminals)
The DC-OK relay contact is synchronized with the DC-OK LED.
See chapter 8 for details.
F “Parallel Use” “Single Use” selector
Set jumper to “Parallel Use” when power supplies are connected in parallel
to increase the output power. In order to achieve a sharing of the load
current between the individual power supplies, the “parallel use” regulates
the output voltage in such a manner that the voltage at no load is approx.
4% higher than at nominal load. See also chapter 22.5. A missing jumper is
equal to a “Single Use” mode.
Apr. 2014 / Rev. 1.4 DS-CPS20.361-EN
All parameters are specified at 36V, 13.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany