Datasheet

CPS20.361
C-Series
36V, 13.3A, SINGLE PHASE INPUT
9. EFFICIENCY AND POWER LOSSES
AC 100V AC 120V AC 230V
Efficiency typ. 92.4% 93.0% 94.3% at 36V, 13.3A
typ. 91.9% 92.7% 94.1% at 36V, 16A (Power Boost)
Average efficiency
*)
typ. 91.4% 91.8% 93.2% 25% at 3.3A, 25% at 6.7A,
25% at 10A. 25% at 13.3A
Power losses typ. 6.8W 5.8W 2.8W at 36V, 0A
typ. 21.0W 20.0W 16.5W at 36V, 6.7A (=50%)
typ. 39.5W 36.1W 29.0W at 36V, 13.3A
typ. 50.8W 45.4W 36.1W at 36V, 16A (Power Boost)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 9-1 Efficiency vs. output current at 36V,
typ.
Fig. 9-2 Losses vs. output current at 36V, typ.
Efficiency
02468 12 16A
88
89
90
91
92
93
94
95
96%
Output Current
10 14
a) 100Vac
b) 120Vac
c) 230Vac
c
a
b
Power Losses
0 4 16A
10
0
20
40
60W
10
30
2 6 8
b
a
50
12 14
a) 100Vac
b) 120Vac
c) 230Vac
c
Output Current
Fig. 9-3 Efficiency vs. input voltage at 36V,
13.3A, typ.
Fig. 9-4 Losses vs. input voltage at 36V,
13.3A, typ.
Efficiency
9/26
120 180 230 264Vac
Power Losses
89
90
91
92
Input Voltage
93
94
95%
120 180 230 264Vac
15
20
25
30
Input Voltage
35
40
45W
100100
Apr. 2014 / Rev. 1.4 DS-CPS20.361-EN
All parameters are specified at 36V, 13.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany