Datasheet

CPS20.361
C-Series
36V, 13.3A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks
AC input range min. 100-264Vac continuous operation
min. 85-100Vac short term or with output derating (1%/V) or with
reduced ambient temperature, see Fig. 15-1,
no damage between 0 and 85Vac
min. 264-300Vac < 500ms
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 84Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 39Vac steady-state value at 3.3A load, see Fig. 3-1
typ. 53Vac steady-state value at 6.7A load, see Fig. 3-1
typ. 74Vac steady-state value at 13.3A load, see Fig. 3-1
AC 100V AC 120V AC 230V
Input current typ. 5.25A 4.36A 2.33A at 36V, 13.3A, see Fig. 3-3
6.33A 5.23A 2.8A at 36V, 16A, see Fig. 3-3
Power factor
*)
typ. 0.99 0.99 0.95 at 36V, 13.3A, see Fig. 3-4
Crest factor
**)
typ. 1.5 1.5 1.65 at 36V, 13.3A
Start-up delay typ. 900ms 850ms 700ms see Fig. 3-2
Rise time typ. 90ms 90ms 90ms at 36V, 13.3A const. current
load, 0mF load capacitance,
see Fig. 3-2
typ. 200ms 200ms 200ms at 36V, 13.3A const. current
load, 15mF load capacitance,
see Fig. 3-2
Turn-on overshoot max. 1V 1V 1V see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Oct. 2013 / Rev. 1.3 DS-CPS20.361-EN
All parameters are specified at 36V, 13.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/25