Datasheet

CS10.241, CS10.241-S1
C-Line
24V, 10A, SINGLE PHASE INPUT
Jul. 2015 / Rev. 2.0 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.12. MOUNTING ORIENTATIONS
Mounting orientations other than the input terminals on the bottom require a reduction in continuous output power
or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime
expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found
below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-4
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
3
9
9
12A
50
A
1
Ambient Temperature
Fig. 22-5
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
3
6
9
12A
50
A
2
Ambient Temperature
A
1
Fig. 22-6
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
3
6
9
12A
50
Ambient Temperature
A
1
A
2
Fig. 22-7
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
3
6
9
12A
50
Ambient Temperature
A
1
A
2
Fig. 22-8
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
3
6
9
12A
50
Ambient Temperature
A
1
A
2
26/26