User manual

CS3.241
CSeries
24V, 3.3A, SINGLE PHASE INPUT
September. 2007 / Rev. 1.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/21
15. EMC
The CE mark is in conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive
(LVD) 73/23/EWG. A detailed EMC Report is available on request.
EMC Immunity
EN 61000-6-2, EN 61000-6-1
Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 L Æ N
N / L Æ PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
500V
500V
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0,15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion B *)
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C
Input voltage swells PULS internal standard 300Vac, 500ms Criterion A
Powerful transients VDE 0160 Over entire load
range
750V, 1.3ms Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
B: The power supply continuous to operate as intended after the test. No degradation of performance or loss of function occur,
when the power supply is used as intended. During the test, degradation of performance is however possible.
C: Temporary loss of function is possible. Power supply might shut-down and restarts by itself. No damages or hazards for the
power supply will occur.
*) Below 2.8A criterion A is fulfilled
EMC Emission
EN 61000-6-3, EN 61000-6-4 Generic standards
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
EN 55022 Class A, output lines
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Fulfilled (Class A)
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching frequency
50kHz to 450kHz Input voltage and load dependent