Datasheet

CS5.244
C-Line
24V, 5A, SINGLE PHASE INPUT
11. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Type
Screw terminals
Solid wire 0.5-6mm
2
Stranded wire 0.5-4mm
2
American Wire Gauge AWG20-10
Max. wire diameter 2.8mm (including ferrules)
Wire stripping length 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-head No 2
Recommended tightening torque 1Nm, 9lb.in
Pull-out force according to UL 486E
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/23