Datasheet

CS5.244
C-Line
24V, 5A, SINGLE PHASE INPUT
14. ENVIRONMENT
Operational temperature
*)
-10°C to +70°C (14°F to 158°F) reduce output power according Fig. 14-1
Storage temperature -40°C to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 1.6W/°C
3W/°C
45°C to 60°C (113°F to 140°F)
60°C to 70°C (140°F to 158°F)
Humidity
**)
5 to 95% r.h. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
***)
IEC 60068-2-6
Shock 30g 6ms, 20g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature,
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating 7.5W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 14-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the
unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 14-1 Output current vs. ambient temp. Fig. 14-2 Output current vs. altitude
0
02040
70°C
1
2
3
4
5
6A
60
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
-10
s
h
o
r
t
t
e
r
m
Allowable Output
Current at 24V
0
0 2000 4000
6000m
1
2
3
4
5
6A
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
C
B
A
s
h
o
r
t
t
e
r
m
Allowable Output
Current at 24V
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/23