21.3. REDUNDANCY MODULES
YRM2.DIODE – (2x 10A Inputs, 1x 20A output)
The YRM2.DIODE is a dual redundancy module, which can be used to build redundant
systems. It is equipped with two input channels, which are individually decoupled by
utilizing diodes.
The YRM2.DIODE does not require an additional auxiliary voltage and is self-powered even
in case of a short circuit across the output.
The YRM2.DIODE has a monitoring circuit included and is the perfect solution when the
power supply has no DC-OK function. Two LEDs and two relay contacts signal when one of
the two DC-input voltages is not in range due to a non-functioning or disconnected power
supply.
Due to the compact design, the unit is very slender and only requires 32mm width on the
DIN-rail.
Fig. 21-1 Typical 1+1 Redundant configuration for 5A load current
Failure
Monitor
5A
Load
optional
I I
L
N
PE
YRM2.DIODE
+
-
OUT
+
-
IN 1
+
-
IN 2
IN 1 IN 2
L N PE
CS5
Power Supply
+ +
- -
24V, 5A
L N PE
CS5
Power Supply
+ +
- -
24V, 5A
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN