4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the QS5.241 unit instead.
5. INPUT INRUSH CURRENT
After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input
inrush current is generated.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current max. 38A
peak
at 230Vac, +40°C ambient, cold start
typ. 30A
peak
at 230Vac, +40°C ambient, cold start
Inrush energy max. 1A
2
s at 230Vac, +40°C ambient, cold start
Fig. 5-1 Typical input inrush current behavior
1 >
2
2 >
3 >
Input: 230Vac
Output: 24V, 5A
Ambient: +40°C
Upper curve: Input current (20A / DIV)
Medium curve: Input voltage (200V / DIV)
Lower curve: Output voltage (10V / DIV)
Time scale: 10ms / DIV
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN