Datasheet

CS5.244
C-Line
24V, 5A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time typ. 161ms at 230Vac, 24V, 2.5A, see Fig. 7-1
min. 128ms at 230Vac, 24V, 2.5A, see Fig. 7-1
typ. 78ms at 230Vac, 24V, 5A, see Fig. 7-1
min. 62ms at 230Vac, 24V, 5A, see Fig. 7-1
typ. 63ms at 230Vac, 24V, 6A, see Fig. 7-1
min. 50ms at 230Vac, 24V, 6A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
25
50
170 200 230 264Vac
Hold-up
Time
100
75
125
Input Voltage
a) 24V 2.5A typ.
b) 24V 2.5A min.
c) 24V 5A typ.
d) 24V 5A min.
e) 24V 6A min.
a
b
c
d
e
150ms
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.