24V, 5A, SINGLE PHASE INPUT
9. LIFETIME EXPECTANCY AND MTBF
Lifetime expectancy
*)
144 000h
*)
at 230Vac, 24V, 2.5A and 40°C
408 000h
*)
at 230Vac, 24V, 2.5A and 25°C
72 000h at 230Vac, 24V, 5A and 40°C
204 000h
*)
at 230Vac, 24V, 5A and 25°C
42 000h at 230Vac, 24V, 6A and 40°C
120 000h
*)
at 230Vac, 24V, 6A and 25°C
MTBF
**)
SN 29500, IEC 61709 940 000h at 230Vac, 24V, 5A and 40°C
799 000h at 230Vac, 24V, 6A and 40°C
1 626 000h at 230Vac, 24V, 5A and 25°C
MTBF
**)
MIL HDBK 217F 680 000h at 230Vac, 24V, 5A and 40°C; Ground Benign GB40
612 000h at 230Vac, 24V, 6A and 40°C; Ground Benign GB40
932 000h at 230Vac, 24V, 5A and 25°C; Ground Bening GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
(NTC)
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany