Data Sheet

QS40.241
Q-Series
24V, 40A, SINGLE PHASE INPUT
12. EFFICIENCY AND POWER LOSSES
AC 100V AC 120V AC 230V
Efficiency typ. 93.2% 93.6% 94.6% at 24V, 40A
Average efficiency
*)
typ. 92.7% 93.0% 93.9% 25% at 10A, 25% at 20A, 25%
at 30A. 25% at 40A
Power losses typ. 3.6W 3.5W 3.3W with activated shut-down
typ. 13.9W 13.1W 13.2W at 24V, 0A (no load)
typ. 36.1W 34.5W 30.6W at 24V, 20A (half load)
typ. 70.0W 65.6W 54.8W at 24V, 40A (full load)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 12-1 Efficiency vs. output current at 24V,
typ.
Fig. 12-2 Losses vs. output current at 24V,
typ.
Efficiency
8 1216202428323640A
88
89
90
91
92
93
Output Current
94
95
96%
1
2
0
V
a
c
1
0
0
V
a
c
230Vac
Power Losses
0 4 8 1216202428 40A
10
0
30
40
50
70
80W
120Vac
100Vac
230Vac
32 36
60
20
Output Current
Fig. 12-3 Efficiency vs. input voltage at 24V,
40A, typ.
Fig. 12-4 Losses vs. input voltage at 24V, 40A,
typ.
Efficiency
85 120
155
190 225 260Vac
89
90
91
92
Input Voltage
93
94
95%
Power Losses
20
30
40
50
60
70
80W
85 120
155
190 225 260Vac
Input Voltage
Oct. 2014 / Rev. 1.2 DS-QS40.241-EN
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/28