Data Sheet
QS40.241
Q-Series
24V, 40A, SINGLE PHASE INPUT
16. FRONT SIDE AND USER ELEMENTS
Fig. 16-1 Front side
A
Input Terminals (Screw terminals)
N, L Line input
...PE (Protective Earth) input
B
Output Terminals (Screw terminals, two pins per pole)
+ Positive output
– Negative (return) output
C “Parallel Use” “Single Use” Selector
Set jumper to “Parallel Use” when power supplies are
connected in parallel to increase the output power. In order
to achieve a sharing of the load current between the
individual power supplies, the “parallel use” regulates the
output voltage in such a manner that the voltage at no load
is approx. 4% higher than at nominal load. See also chapter
25.6. A missing jumper is equal to a “Single Use” mode.
D
Output Voltage Potentiometer
Multi turn potentiometer;
Open the flap to set the output voltage.
Factory set: 24.1V at full output current, “Single Use” mode.
E
DC-OK LED (green)
On, when the voltage on the output terminals is >90% of the
adjusted output voltage
F Overload LED (red)
- On, when the voltage on the output terminals is <90% of
the adjusted output voltage, or in case of a short circuit in
the output.
- Flashing, when the shut-down has been activated or the
unit has switched off due to over-temperature.
- Input voltage is required
G
DC-OK Relay Contact
The DC-OK relay contact is synchronized with the DC-OK LED.
See chapter 8 for details.
H
Shut-down and Remote Control Input
Allows the power supply to be shut down. Can be activated
with a switch contact or an external voltage.
The remote control input allows adjusting the output voltage
between 22V and 28V. See chapter 9 and 10 for details.
Indicators, LEDs
Overload LED DC-OK LED DC-OK Contact
Normal mode OFF ON Closed
During BonusPower
®
OFF ON Closed
Overload (Hiccup mode) flashing OFF Open
Output short circuit flashing OFF Open
Temperature Shut-down flashing OFF Open
Active Shut-down input flashing OFF Open
No input power OFF OFF Open
Oct. 2014 / Rev. 1.2 DS-QS40.241-EN
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/28