Data Sheet
QS40.241
Q-Series
24V, 40A, SINGLE PHASE INPUT
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 54ms 54ms 54ms at 24V, 20A, see Fig. 7-1
min. 45ms 45ms 45ms at 24V, 20A, see Fig. 7-1
typ. 27ms 27ms 27ms at 24V, 40A, see Fig. 7-1
min. 23ms 23ms 23ms at 24V, 40A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
10ms
20ms
30ms
40ms
60ms
90 120 155 190 230Vac
Input Voltage
50ms
Hold-up Time
24V, 40A, typ.
24V, 20A, min.
24V, 20A, typ.
24V, 40A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Oct. 2014 / Rev. 1.2 DS-QS40.241-EN
All parameters are specified at 24V, 40A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.