Datasheet
sl10e110 / 050318 1/2
Data sheet
20A single phase
SL20.110/.111
• Input: AC 115/230V Auto Select
• Output: 24...28V / 480W (600W)
• 90% Efficiency
• Ideal for parallel operation
• Overload behaviour adjustable!
(Continuous current / Hiccup)
Input
Efficiency, Reliability etc.*
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Input voltage AC 100-120V/200-240V, 47-63Hz
Auto Select
Rated tolerances
• Continuous
operation
• Short-term (1 min)
at 24V/20A
AC 85-132V resp. AC 184-264V
AC 85-140V resp. AC 170-280V
Input current I
n
<10A (115V range)
<5A (230V range)
Inrush current limiting with active bypass of the limiting resistor (NTC).
Inrush current I
pk
<18A at AC 264V (T
amb
= +25°C, cold start)
<37A at AC 264V (T
amb
= +50°C, cold start)
Fuse loading I²t <5A
2
s (T
amb
= +25°C, cold start)
<8A
2
s (T
amb
= +50°C, cold start)
To be fused with a 16A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines).
Harmonic current
emissions (PFC)
SL20.110: no
SL20.111: acc. to EN 61000-3-2
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750V / 1.3ms), for all load conditions.
Hold-up time 30ms at 24V/20A, AC 230Vin
30ms at 24V/20A, AC 120Vin
15ms at 24V/20A, AC 100Vin
Efficiency typ. 90% (AC 230V, 24V/20A)
Losses typ. 53W (AC 230V, 24V/20A)
MTBF 519.000h acc. to Siemensnorm SN29500
(24V/20A, 230V, T
amb
= 40°C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability, as
• only five aluminium electrolytics and
• no small aluminium electrolytics are used.
Output
Construction / Mechanics*
Output voltage DC 24...28V, adjustable by (covered) front
panel potentiometer. Adjust. range guaran-
teed
Output noise
suppression
EN 61000-6-3 (class B) is fulfilled even when
using long, unscreened output cabels
Ambient temperature
range T
amb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling:
•T
amb
=0°C - 60°C 24V/20A resp. 28V/18A
short-term (<30s) 24V/25A resp. 28V/22A
Derating 12W/K (at T
amb
= 60-70°C)
Voltage regulation better than 2% over all
Ripple
• Output charact. S
• Output charact. P
(S/P: Single/Parallel Mode)
(incl. spikes (20MHz bandw.), 50Ω measurem.)
<20mV
PP
(<0.1%)
<40mV
PP
(In: AC 230V, Out: 24V/20A)
<100mV
PP
(In: AC 184V, Out: 24V/20A)
Over-voltage protection At 31V ± 3%: switch to hiccup mode
Front panel indicators:
• Green LED on, when V
out
> U
T
, where U
T
is appr. 2V below V
out
adjusted (24V...28V)
• Red LED on, when V
out
< U
T
Parallel operation Yes, up to ten SL20
To achieve current sharing:
• Plug jumper into pos. 'Output parallel use'. This alters the output
V/I characteristic to be 'softer' (25V at 0.4A, 24V at 20A). The out-
put voltage can still be adjusted.
• Missing jumper = 'parallel use', i.e. 'soft' characteristic
Power back immunity max. 30V
Housing dimensions and Weight
• W x H x D
• Free space for
ventilation
•Weight
220mm x 124mm x 102mm (+ DIN rail)
above/below 70mm recommended
left/right 25mm recommended
1.8kg (SL20.110) resp.
2.5kg (SL20.111)
Design advantages:
• All connection blocks are easy to reach as mounted at the front
panel.
• PVC insulated cable can be used for all connections, as the connec-
tion blocks are mounted in the cooler area on the underside of the
unit.
Order information
Order number
SL20.110 (without PFC)
SL20.111 (including PFC)
Description
SLZ02 (wall mounting set; contains 2 pcs.)
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 60950
18 WM, 60°C
Directive
CB
scheme
IEC60950
Type approval
• IEC / EN60950
• EN50178
• EN60204
acc. to:
Overvolt. cat. III