More Power: 30 A
SL30.300
Input: 3 AC 400...500V
Output: 24...28V / 720W
92.5% efficiency
Ideal for parallel operation
Simple fusing
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No. 60950
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Efficiency, Reliability etc. *
Output
Construction / Mechanics *
* For further information see data sheets „The SilverLine“,
„SilverLine Family Branches“ and mechanics data sheet
Input voltage 3 AC 400...500 V, ± 15 %
47-63 Hz,
Suitable for IT power systems
Rated Tolerances
Continuous
operation
Short term (1 min)
at 24 V/30 A
340-576 V AC resp.
450-820 V DC
300-620 V AC resp.
420-890 V DC
Input current 3 x 2.0 A
Inrush current < 17 A bei 576 V AC
Inrush current limiting done with a fixed 47R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimised. That
means no reset time even at a warm-start.
Fuse loading < 2 A
2
s
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
acc. EN 61000-3-2
Transient
handling
Active transient filter incorporated, so tran-
sient resistance acc.to VDE 0160 / W2 (1560 V /
1.3 ms), for all load conditions.
Hold up time > 10 ms
at 400 V AC, 24 V / 30 A
Efficiency typ. 92.5 % (400 VAC, 24 V / 30 A)
Losses typ. 60 W (400 VAC, 24 V / 30 A)
MTBF 425,000 h @ 400 VAC, 360,000 h @ 480 VAC
(Siemensnorm SN 29500 (Release 07.97),
24 V/30 A, T
amb
= +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
only four aluminium electrolytics and
no small aluminium electrolytics are used.
Output voltage 24...28 V DC, adjustable by (covered) front
panel potentiometer. Adj. range guaranteed
Output noise
suppression
EN 61000-6-3 (class B) is fulfilled even when
using long, unscreened output cabels
Ambient temperature
range T
amb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
at T
amb
=0°C - 60°C 24 V / 30 A (720 W) resp. 28 V / 26 A (728 W)
Derating typ. 18 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation better than 2% over all
Ripple
Output charact. S
Output charact. P
(S/P Single/Parallel Mode)
(incl. spikes (20 MHz bandw.), 50 measurem.)
< 20 mV
PP
(< 0.1 %)
< 40 mV
PP
(In: 230VAC, Out: 24V/30A)
< 100 mV
PP
(In: 184VAC, Out: 24V/30A)
Over-voltage protection At 32 V ± 10%: switch to hiccup mode
Front panel indicators: Green LED on, when V
out
> U
T
, where U
T
is
ca. 2 V below Vout adjusted (24V...28V)
Red LED on, when 10 V < V
out
< U
T
Red LED flashes, when 0 V < V
out
< 10 V
Parallel operation Yes, up to ten SL30 units
To achieve current sharing the output V/I characteristic can be altered
to be 'softer' (25V at 0.4A, 24V at 30A). This is done by repositioning a
bridge connection (without opening the unit).
Power Back Immunity 35 V
Housing dimensions and Weight
•W x H x D
Free space for
ventilation
•Weight
240 mm x 124 mm x 112 mm (+ DIN rail)
above/below 70 mm recommended
left/right 25 mm recommended
2.0 kg
Design advantages:
All connection blocks are easy to reach as mounted at the front panel.
PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
Order information