Datasheet

sl40e300 / 040211 1/2
Data sheet
Order information
Order number Description
SL40.300
SL40.301
SLZ01
basic version, passive load sharing
with signal/measurement outputs, signal output connector included: Order number XFB-S-W8-MSTB 06-W8)
Screw mounting set, two needed per unit
Clever Power
SL40.300/.301
Input: 3 AC 400...500V
Output: 24...28V / 960W (1080W)
No switch-off at overload
Ideal for parallel operation
Output for measurement and
logical signals (.301)
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 950-M90
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Construction / Mechanics *
Output (signal outputs see overleaf)
Efficiency, Reliability etc. *
Input voltage 3 AC 400...500 V, – 15 %, + 15 %
47-63 Hz, Suitable for IT power systems
Rated Tolerances
Continuous operat.
Short term (1 min)
at 24 V/40 A
340-575 V AC
300-620 V AC
Input current 3.0 A
Inrush current < 30 A
Inrush current limiting done with a fixed 23R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimized. That
means no reset time even at a warm-start.
Fuse loading 3 A
2
s
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
acc. EN 61000-3-2
Transient
handling
Active transient filter incorporated, so tran-
sient resistance acc.to VDE 0160 / W2 (1300 V /
1.3 ms), for all load conditions.
Hold up time min. 15 ms
at 400 V AC, 24 V / 40 A
Housing dimensions and Weight
•W x H x D
Free space for
ventilation
•Weight
275 mm x 124 mm x 117 mm (+ DIN rail)
above/below each 70 mm recommended
left/right each 25 mm recommended
3.3kg
Connections
(input and output)
robust screw terminals, connector size range:
solid: 1.5...6 mm
2
(Outp.: 0.5...16 mm
2
)
flexible: 1.5...4 mm
2
(Outp.: 0.5...10 mm
2
)
Output: Minus terminal with 2 connectors,
current handling per output: 40 A (max. acc.
to UL) resp. 56 A (max. acc. to VDE)
Design advantages:
All connection blocks mounted on front panel for ease of access.
PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
Power density: 230 W per litre housing volume.
Output voltage 24...28 V DC, adjustable by (covered) front
panel potentiometer. Adj. range guaranteed
Output noise
suppression
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range T
amb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
•T
amb
=0°C - 60°C
•T
amb
=0°C - 45°C
24 V / 40 A (960 W) resp. 28 V / 35 A (980 W)
24 V / 45 A (1080 W) resp. 28 V / 38 A (1064 W)
short-term (< 1 min.) also at 60°C admissible
Derating typ. 24 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation better than 2% over all
Ripple (incl. spikes) < 50 mV
PP
(20 MHz bandw., 50 measurem.)
Over-voltage protectionAt 32 V ± 10%: switch to hiccup mode
Front panel indicators: Green LED on, when V
out
> U
T
, where U
T
is
ca. 2 V below Vout adjusted (24V...28V)
Red LED on, when V
out
< U
T
Parallel operation SL40.300: yes, no active current sharing
SL40.301: yes, active current sharing, please re-
fer to “Output Signaling” - “Current Balance”
Current sharing by balancing line (active sharing principle, SL40.301) or
’soft’ output characteristic (passive sharing principle, SL40.300; charac-
teristic switch-over by jumper as in SL20/SL30 without opening the unit)
Power Back Immunity < 35 V
Efficiency typ. 92.5% (400 VAC, 24 V / 40 A)
Losses typ 78 W (400 VAC, 24 V / 40 A)
MTBF SL40.300: 305,000 h SL40.301: 268,000 h
acc. to Siemensnorm SN 29500
(24 V/40 A, 400 VAC, T
amb
= +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
only 6 aluminum electrolytics and
no small aluminum electrolytics are used.

Summary of content (2 pages)