Datasheet
sl40e300 / 040211 1/2
Data sheet
Order information
Order number Description
SL40.300
SL40.301
SLZ01
basic version, passive load sharing
with signal/measurement outputs, signal output connector included: Order number XFB-S-W8-MSTB 06-W8)
Screw mounting set, two needed per unit
Clever Power
SL40.300/.301
• Input: 3 AC 400...500V
• Output: 24...28V / 960W (1080W)
• No switch-off at overload
• Ideal for parallel operation
• Output for measurement and
logical signals (.301)
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 950-M90
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Construction / Mechanics *
Output (signal outputs see overleaf)
Efficiency, Reliability etc. *
Input voltage 3 AC 400...500 V, – 15 %, + 15 %
47-63 Hz, Suitable for IT power systems
Rated Tolerances
• Continuous operat.
• Short term (1 min)
at 24 V/40 A
340-575 V AC
300-620 V AC
Input current 3.0 A
Inrush current < 30 A
Inrush current limiting done with a fixed 23R resistor (not a thermistor)
which is bridged after the unit is running, so losses are minimized. That
means no reset time even at a warm-start.
Fuse loading 3 A
2
s
To be fused with a 3 x 10A, B-type 'circuit-breaker' switch based on the
usual thermomagnetic overload sensing principle (used anyway to fuse
the input lines; unit has no internal fuses).
Harmonic current
emissions (PFC)
acc. EN 61000-3-2
Transient
handling
Active transient filter incorporated, so tran-
sient resistance acc.to VDE 0160 / W2 (1300 V /
1.3 ms), for all load conditions.
Hold up time min. 15 ms
at 400 V AC, 24 V / 40 A
Housing dimensions and Weight
•W x H x D
• Free space for
ventilation
•Weight
275 mm x 124 mm x 117 mm (+ DIN rail)
above/below each 70 mm recommended
left/right each 25 mm recommended
3.3kg
Connections
(input and output)
robust screw terminals, connector size range:
• solid: 1.5...6 mm
2
(Outp.: 0.5...16 mm
2
)
• flexible: 1.5...4 mm
2
(Outp.: 0.5...10 mm
2
)
Output: Minus terminal with 2 connectors,
current handling per output: 40 A (max. acc.
to UL) resp. 56 A (max. acc. to VDE)
Design advantages:
• All connection blocks mounted on front panel for ease of access.
• PVC insulated cable can be used for all connections, as the connection
blocks are mounted in the cooler area on the underside of the unit.
• Power density: 230 W per litre housing volume.
Output voltage 24...28 V DC, adjustable by (covered) front
panel potentiometer. Adj. range guaranteed
Output noise
suppression
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range T
amb
Operation: 0°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Rated continuous loading with convection cooling
•T
amb
=0°C - 60°C
•T
amb
=0°C - 45°C
24 V / 40 A (960 W) resp. 28 V / 35 A (980 W)
24 V / 45 A (1080 W) resp. 28 V / 38 A (1064 W)
short-term (< 1 min.) also at 60°C admissible
Derating typ. 24 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation better than 2% over all
Ripple (incl. spikes) < 50 mV
PP
(20 MHz bandw., 50 Ω measurem.)
Over-voltage protectionAt 32 V ± 10%: switch to hiccup mode
Front panel indicators: • Green LED on, when V
out
> U
T
, where U
T
is
ca. 2 V below Vout adjusted (24V...28V)
• Red LED on, when V
out
< U
T
Parallel operation SL40.300: yes, no active current sharing
SL40.301: yes, active current sharing, please re-
fer to “Output Signaling” - “Current Balance”
Current sharing by balancing line (active sharing principle, SL40.301) or
’soft’ output characteristic (passive sharing principle, SL40.300; charac-
teristic switch-over by jumper as in SL20/SL30 without opening the unit)
Power Back Immunity < 35 V
Efficiency typ. 92.5% (400 VAC, 24 V / 40 A)
Losses typ 78 W (400 VAC, 24 V / 40 A)
MTBF SL40.300: 305,000 h SL40.301: 268,000 h
acc. to Siemensnorm SN 29500
(24 V/40 A, 400 VAC, T
amb
= +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
High reliability and lifetime, as
• only 6 aluminum electrolytics and
• no small aluminum electrolytics are used.