Data Sheet
UZK12.071, UZO12.07
U-Series
BATTERY MODULE 12V, 7AH
11. ENVIRONMENT
Operational temperature
*)
-10°C to +40°C (14°F to 104°F) For charging
Frequently charging below +5°C (41°F) reduced
the lifetime of the battery
-15°C to +50°C (5°F to 122°F) For discharging
Storage temperature
-20°C to +50°C (-4°F to 122°F) For storage and transportation
Recommendation:
Do not store at temperatures higher than 25°C
or performance and lifetime may change.
Humidity 5 to 95% r.h. IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal ±4mm at 16.7Hz
fixed frequency for 1hour
Vibration in vertical mounting orientation
according to IEC/EN 61056-1
Shock free fall from 20cm
onto a wooden floor
Shock with bottom down orientation
according to IEC/EN 61056-1
Altitude 0 to 6000m (0 to 20 000ft)
Degree of pollution 2 According to IEC 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Corrosive gases ISA-71.04-1985, Severity Level G3
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
12. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Power terminals
Type
Screw terminals
Maximal wire size, solid wire 4mm
2
Maximal wire size, stranded wire 4mm
2
American Wire Gauge AWG 12-10
Maximal wire diameter 3.5mm (including ferrules)
Wire stripping length 7mm / 0.28inch
Screwdriver Slotted 3.5x0.5mm
Recommended tightening torque 0.5Nm, 4.5lb.in
Instructions:
a) Follow national installation codes and installation regulations!
b) Ensure that all strands of a stranded wire enter the terminal connection!
c) Unused terminal compartments should be securely tightened.
d) Ferrules are allowed.
Aug. 2017 / Rev. 2.2 DS-UZK12.071
All parameters are typical values specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/11