Manual
10.6 Analog Input Calibration
If you are not using the 4-20mA input to the MPC for control, skip this
section. To calibrate the Input Current you must first correctly wire an
external signal source. Refer to the Control Input/Output Signal
Wiring Section (8.4.8). To perform a calibration, the signal-generating
device must be active and capable of generating the full range (low to
high) of potential input signals.
1. The starting display will be:
SETPT XX.XXX
FLOW XX.XXX
2. Press the MENU key
-MENU-
CALIBRATION
3. Press the ENTER key
CALIBRATION
PUMP FLOW
4. Press the UP arrow key twice, to access the analog input calibration
CALIBRATION
ANALOG INPUT
5. Press the ENTER key
APPLY MIN MA
ENTER TO START
6. Apply your desired minimum mA control signal to the MPC (usually 4
mA)
7. Press the ENTER key
MIN SETPT X.XX MA
SPEED 000.0%