Manual

38
Press [ENTER} to accept the {DISABLED} setting. The display will return to the {– MENU – /
OVER TEMPERATURE} screen.
– MENU –
OVER TEMPERATURE
7.2.9 Power Failure Set Up
This sub-menu allows you to configure the way the DLC–XP/RC reacts to a power outage. During
the power up stage, your system can either:
Return to settings that were active when the pump lost power, or
Shut the motor off.
A power outage is defined as the loss of power when ever the DLC is not in {MOTOR OFF} state.
1. Press the [MENU] key and [UP] eight times until the display reads {MENU / POWER FAILURE}.
–MENU–
POWER FAILURE
Press [ENTER] to go the power failure response sub-menu.
2. The display prompts you for the Power-up status.
a) To keep the prior settings the power is returned to the unit (after a power failure), select the
{PRIOR SETTINGS} option.
DURING POWER UP
PRIOR SETTINGS
Press [ENTER] to accept.
b) If you do want to return to prior settings and would like to shut the motor off, press [UP] to scroll
to {MOTOR OFF}.
DURING POWER UP
MOTOR OFF
Press [ENTER] to accept.
3. The display will return to the {MENU / POWER FAILURE} screen.
7.2.10 Alarm Relay
This sub-menu sets up the alarm relay output as normally open or normally closed.
1. Press the [MENU] key. Press [UP] nine times until the {MENU / ALARM RELAY} appears. Press
[ENTER] to continue to program the Alarm Relay sub-menu.
–MENU–
ALARM RELAY
2. The alarm relay can be configured as {NORMALLY OPEN}. With this setting the relay will CLOSE
when the alarm output is activated.
RELAY OUTPUT
NORMALLY OPEN
If you would rather have the relay OPEN when the output is activated, press the [UP] arrow key to
change the configuration to {NORMALLY CLOSED}.
RELAY OUTPUT
NORMALLY CLOSED
When you have finished making your selection, press [ENTER] to accept.
3. The display returns to the {-MENU- / ALARM RELAY}.