User Instructions

2
Table 2. Technical parameters.
450V AC max
Max. 10mm
Max. 2,5mm
2
IP20
DC01 1mm steel plate, color RAL 3001 (red)
190 x 80 x 30 [mm] (WxHxD)
-25ºC for +60ºC
136mm Φ5,5 mm
0,52kg /0,55 kg
2. Installation.
The junction box for fire alarm systems should be mounted directly to the concrete base class min. B20 or
natural stone. Other building materials of adequate strength and of fire resistance class of at least R90 are also
approved for use.
The junction box for fire alarm systems should be mounted to the ceiling or wall using two steel pins of
adequate fire resistance. The cables should be mounted using handles at intervals of 600 mm. Mounting distance
between the cables (handles) and the edge of the junction box is maximally 100 mm.
Pay attention to the following boundary conditions:
a) The bushings and expansion bolts should be recessed at least 30 mm into the concrete.
b) Tension on the pin should not exceed 500 N.
c) Alternatively, the pins with well-documented fire protection design can also be used.
d) It should be ensured that the functional class of the cable assemblies containing junction boxes for fire
alarm systems will not be adversely affected by falling building elements.
Installation cables should be led through the appropriate bushings and then mounted with cable holders
located inside the enclosure.
Pulsar sp j.
Siedlec 150, 32-744 Łapczyca, Poland
Phone (+48) 14-610-19-40, Fax (+48) 14-610-19-50
E-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
WEEE LABEL
Waste electrical and electronic equipment must not be disposed of with normal household waste. According to the European Union WEEE
Directive, waste electrical and electronic equipment should be disposed of separately from normal household waste.