Data Sheet
Table Of Contents

AWZ 512 v.2.1/VI
PU2 Relay module
CODE:
NAME:
DESCRIPTION
The PU2 (AWZ512) relay module is to be used in low-voltage installations. It is intended for controlling
and status indication in e.g. alarm or access control systems. It may be used to control devices of high power
consumption via OC outputs of alarm systems. Moreover, it ensures galvanic isolation of signals, power
sources relating to the outputs of the module.
SPECIFICATIONS
EN
Tel.( +48)14-610-19-40, fax:( +48)14- 610-19-50, www.pulsar.pl, e-mail:sales@pulsar.pl
Relay module
AC/DC power
Pulsar
®
Voltage of the relay’s coil
10÷16V DC/ 10÷13V AC (-/+5%),
Current of the relay’s coil
30mA@12VDC
Number of relays
2
Voltage of the relay’s
contacts
30VDC / 50VAC max.
Current of the relay’s
contacts
1A max.
Fuse F1 – F2
2 x F 1,5A
Operating conditions
2nd environmental class, -10°C÷ 50°C
Dimensions
L=80, W=43, H=20 [mm, +/-2]
Net/gross weight
0,04 / 0,07 [kg]
Installation:
Iinstallation tape or installation bolt x2
Declarations, warranty
CE, 2 year from the production date
Notes
leads on connections:Ø 0,41÷1,63 (AWG 26-14),