User Instructions

2
3. Specifications.
10V ÷ 15V DC
5 mA
4s/1min/16min/4h 15min (+/-10%)
0V ÷30V AC
Inactive input: 0V ÷1V AC
Active input: 5V ÷30V AC
GND= ‘VDC-power terminal
OC type 50mA max.
normal state: L (0V, GND),
active state: hi-Z (high impedance)
normal state: hi-Z (high impedance)
active state: L (0V, GND)
L1 green LED
II environmental class, -10°C ÷ 50°C
L=60, W=43, H=23 [mm, +/-2]
A mounting panel with an adhesive
tape,mounting screws x2 (holes 3mm)
Ф0,41÷1,63 (AWG 26-14)
0,03kg /0,05 kg
CE, RoHS, 2 year from the production date
Fig.2. The view of the PC2 module.
4. Installation.
The module is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and
required for a given country) for 230V/AC and low-voltage installations. The unit should be mounted in confined spaces,
in accordance with the II environmental class, with normal relative humidity (RH=90% maximum, without condensation)
and temperature from -10°C to + 50°C.
The device shall be mounted in a metallic enclosure (a cabinet, a final case). In order to fulfil LVD and EMC requirements,
the rules for: power-supply, encasing and screening shall be followed, according to application.
1. Mount the enclosure (cabinet etc.) and lead the cables through the cable ducts.
2. Install the PC2 time module on the installation terminal.
3. Lead the DC supply power to the +VDC, -VDC terminals, keep polarisation.
4. Lead the AC controlled power to the AC1 terminal.
5. Connect the AC power loss signal: OC1 or OC2 (depending on application requirements) to the indicating device
(LED, transmitter’s input, control panel’s input, indicator, etc.)
6. With Z1, Z2 jumpers, choose the indication delay time of the OC1 and OC2 outputs.
7. Once the tests and operation control have been completed, the enclosure / cabinet can be locked.
Pulsar
Siedlec 150, 32-744 Łapczyca, Poland
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
WEEE PARKING
According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste
and to collect such WEEE separately.
Zużytego sprzętu elektrycznego i elektronicznego nie wolno wyrzucać razem ze zwykłymi domowymi odpadami. Według dyrektywy WEEE
obowzującej w UE dla zużytego sprzętu elektrycznego i elektronicznego należy stosować oddzielne sposoby utylizacji.